3

When programming the MSI-30B with the FPI-32 Field
Programmer, you must first determine the software
revision of the Field Programmer. This is done by
powering up the FPI-32 and reading the software
revision shown on the display.

The Test and Menu Modes are the same for FPI-32
Revision 1.2 and 1.3 software.

With revision 1.2 software,

 use the following proce-

dure for programming Two Stage Manual Stations
(MSI-30B) using the FPI-32 Field Programmer.

PROGRAM MODE:

1.

Select 1 = MXL mode for programming the device
addresses.

NOTE:

System XL3 does not support the use of

the MSI-30B manual station. Therefore, the XL3
programming mode should never be used.

2.

Select the address required for the keyswitch
(second address). The device automatically
defaults the first address (pull station) to the
selected address minus one.

Example:

If the required address for the device

is 10 and 11, select address 11 in the program
mode and the FPI-32 will address the device to 10
and 11.

NOTE:

Revision 1.2 software does not allow the

programming of an MSI-30B to addresses 59 and
60. Do not use this combination.

With revision 1.3 software,

 use the following proce-

dure for programming Two Stage Manual Stations
(MSI-30B) using the FPI-32 Field Programmer.

PROGRAM MODE:

1.

Select 1 = MXL mode for programming the device
addresses.

NOTE:

System XL3 does not support the use of

the MSI-30B manual station. Therefore, the XL3
programming mode should never be used.

2.

Select the address required for the pull  station
(first address). The device automatically defaults
the second address (key switch) to the selected
address plus one.

Example:

If the required address for the device

is 10 and 11, select address 10 in the program
mode and the FPI-32 will address the device to 10
and 11.

TEST MODE:

Test mode does not thoroughly test the device. This
mode only tests the first address of the unit. For more
complete testing, use the menu mode.

MENU MODE:

Test

This test mode only checks that the device is respond-
ing. For complete testing, move on to the analog
portion of menu mode.

Analog

When selecting

 READ ANALOG RESPONSES

 in the

menu mode, you can read the actual voltages being
sent by the device. The programmer allows you to
toggle between the two addresses by press-ing the

NO 

key. After selecting an address, press the 

YES

key to display the voltages. The voltage windows for
the MSI-30B are:

CAL

3.75 – 4.25

ID

7.12 – 8.00

ID-2

5.12 – 6.00

A2 (STBY)

0.63 – 5.88

A2 (ALARM)

6.00 – 8.00

Programming Instructions

MODEL MSI-30B  Manual Station