Configuring the MT8001
38
Building Technologies
048_DMS_MT8001_ICC_MP4.20_A6V10096181_a_en.doc
Fire Safety & Security Products
06.2009
Fig. 37 MT8001 Options tab
5.4.2
Defining event behaviour – Approvals tabs
5.4.2.1 Approvals and intrusion options – Duress Alarms
Configure the Approvals-1 tab (see Fig. 38) if specific
EN54
or
ULC Approvals
are
required for the MT8001 Management Terminal
AND/OR
if you need to configure a Duress Alarm on the MT8001.
MT8001 Approvals 1 tab
Configuration options
Approvals
Disable event duplication
Select if you want a duplicate event from the
same point to override the primary event and
display only one event in the Event list instead
of two.
PIZ Approvals
Not
available
EN54 Approvals
Select if EN54 Approvals are required
ULC Approvals
Select if ULC Approvals are required
Intrusion Options – Duress Alarm
Duress Alarm transmission
Select to enable a Duress Alarm
Duress events suppression time
Duress feedback delay (in seconds) before the
Duress Alarm appears on the MT8001
Default: 300 seconds
Intrusion Options – Terminal access
ULC
Key switch enabled
ULC applications: This box
must
be checked
Other applications: Optional
Intrusion Options – Resetting of Sabotage
Alarms
Sabotage Reset enabled
Enable the Reset button after a Sabotage event
2