5.4.2.2 Intrusion options – PIN code violations
Configure the Approvals-2 tab (see Fig. 39) to define a PIN code violation Alarm on
the MT8001.
To configure a PIN code violation Alarm, do the following:
1.
Check the
PIN code violation Alarm
to enable a local Alarm on the MT8001.
2.
Modify the
User lockout time
(in seconds), if desired.
Note:
During this time, additional logins are prevented.
3.
Check the
PIN code Alarm transmission
to enable remote transmission of the
Alarm.
4.
Drag and drop the appropriate node from the Composer tree to the Approvals-2
tab window.
Note:
Typically, the node will be a point on an intrusion panel.
5.
In the
Drop Point
dialog box, do the following:
a.
Choose a property from the
Property
drop-down list.
b.
Choose a command from the
Command
drop-down list.
c.
Change the timeout (command feedback), if desired.
6.
Select
Add
.
Note:
To update the list in the
Drag and Drop
window, select the node, and then
select
Change
or
Remove
.
Fig. 39 Approvals-2 tab