Technical information
8.3 Electromagnetic compatibility
Unified Comfort Panels
144
Operating Instructions, 03/2020, A5E46641217-AA
8.3
Electromagnetic compatibility
The device fulfills, amongst others, the requirements of the EMC directive applicable to the
European domestic market.
Installing the device according to EMC directive
EMC-compliant mounting of the device and the use of interference-proof cables provide the
basis for interference-free operation.
Observe the following manuals in addition to these operating instructions:
●
Designing interference-free controllers
https://support.industry.siemens.com/cs/ww/en/view/59193566
●
Industrial Ethernet/PROFINET – Passive network components
https://support.industry.siemens.com/cs/ww/en/view/84922825
Pulse-shaped disturbance
The following table shows the electromagnetic compatibility of the modules with regard to
pulse-shaped interference. The precondition for electromagnetic compatibility is that the
device meets the specifications and guidelines for electrical installation.
Pulse-shaped interference
Tested with
Degree of severity
Electrostatic discharge
in accordance with IEC 61000-4-2
Air discharge: 8 KV
3
Contact discharge: 6 kV (front)
Contact discharge: 4 kV (rear)
2
Bursts
(high-speed transient interference)
in accordance with IEC 61000-4-4
2 kV power supply line
2 kV signal line, > 30 m
1 kV signal line, < 30 m
3
High-energy single pulse (surge) in
accordance with IEC 61000-4-5
1
Asymmetrical coupling:
•
1 kV supply line, DC voltage
•
1 kV signal line/data cable, > 30 m
2
Symmetrical coupling:
•
0.5 kV power cable, DC voltage
•
1 kV signal line, > 30 m,
2
1
External protective circuit required, see Function Manual "Designing Interference-free Controllers",
section 7 "Lightning and overvoltage protection"
You can find the Function Manual "Designing interference-free controllers" for download on
the Internet (