background image

 

 

Performing a firmware update on MultiRanger 200 HMI 

5

 

Application examples, 09\2020, AG061215 

2

 

Procedure 

2.1

 

Updating Firmware 

 

 

Note 

 

Two firmware packages are provided with MultiRanger 200 HMI, one for the sensor board 
and one for the HMI (display). 

 

Downloading an HMI BS2 into the sensor will result in an error. 

 

The HMI software has an estimated download time of 2 hours. 

 

1.

 

Before using the USB to RS-232 adapter for the first time, ensure the driver has been 
installed on your computer. 

2.

 

Disconnect MultiRanger 200 HMI from the power source. 

3.

 

Connect the RJ-11 telephone cable to your PC. This may require the use of an RS-232 to USB 
converter. 

4.

 

Connect MultiRanger 200 HMI to the power source. 

5.

 

Ensure the communication parameters are set as follows: 

 

Parameter 

Setting 

Parameter description 

4.1 Communications Port Se-

lector 

1, RS-232 port (RJ-11 modular 

telephone) 

Sets the communications port 

index for all parameters appli-

cable to this sub-menu. 

4.2 Device Address 

Sets the unique identifier of the 

MultiRanger on the network. 

4.4 Protocol 

Modbus RTU Slave Device 

Sets the communications pro-

tocol used between the Multi-

Ranger and other devices. 

4.5 Serial Baud Rate 

115.200 

Sets the communication rate 

with the master device. 

4.6 Parity 

No parity 

Sets the serial port parity. 

4.7 Data Bits 

Sets the number of data bits 

per character. 

4.8 Stop Bits 

Sets the number of bits be-

tween the data bits. 

6.

 

Right-click on the downloader and select 

Run as administrator

Summary of Contents for MultiRanger 200 HMI

Page 1: ...Performing a firmware update on MultiRanger 200 HMI Application examples 09 2020 AG061215 Introduction 1 Procedure 2 ...

Page 2: ...ated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Sieme...

Page 3: ...ming a firmware update on MultiRanger 200 HMI Application examples 09 2020 AG061215 3 Table of contents 1 Introduction 4 1 1 Objective 4 1 2 Equipment 4 1 3 Disclaimer 4 2 Procedure 5 2 1 Updating Firmware 5 ...

Page 4: ...iRanger 200 HMI 1 2 Equipment Equipment Article No MultiRanger 200 HMI 7ML5033 Dolphin cable adapter DB 9 to RJ 11 2 1b telephone cable 7ML1830 MC RJ 11 telephone cable A PC with a RS 232 serial port USB to RS 232 adapters work too Administrator rights on your PC The firmware image in BS2 format A downloader 1 3 Disclaimer Note While every effort is made to verify the following information no warr...

Page 5: ...B converter 4 Connect MultiRanger 200 HMI to the power source 5 Ensure the communication parameters are set as follows Parameter Setting Parameter description 4 1 Communications Port Se lector 1 RS 232 port RJ 11 modular telephone Sets the communications port index for all parameters appli cable to this sub menu 4 2 Device Address 2 Sets the unique identifier of the MultiRanger on the network 4 4 ...

Page 6: ...ill then see the communications options dialog box Please choose the following options Set slave address to 1 for sensor board or 2 for HMI Set the com port to PC Set the baud rate to 115200 Set other communications to 8 data bits no parity and 1 stop bit 9 Click Next 10 Click Start to begin the download 11 Once the download is complete the following window will appear Click OK ...