background image

 

GAMMA 

instabus

 

Technical product information 

July 2008 

Switching actuator, submodule N 512/21 

5WG1 512-1AB21 

3x AC 230/400V, 16A, C-load, load-check  

 

Siemens AG 

N 512/21, 4 pages 

Technical manual 

Industry Sector, Building Technologies 

Electrical Installation Technology 

© Siemens AG 2008 

Update: http://www.siemens.com/gamma 

P.O. Box 10 09 53, D-93009 Regensburg 

Subject to change without further notice 

 

 

2.4.3.3/1 

Product and functional description 

 
 

 

 

The switching actuator submodule N 512/21 is a 3 MU 

(module units) wide device for DIN-rail mounting in N-

system dimensions, with 3 switching outputs (relay con-

tacts) for AC 230/400V, 16A, C-load, each with load cur-

rent measurement and monitoring (load-check). A sub-

module  cannot  be  operated  stand-alone or be directly 

connected to the bus. But it can be connected via a spe-

cial 6-pole bridging connector either with a switching 

actuator main module or with another submodule which 

is already connected to a main module (see figure 1). 

The submodule electronics are supplied by bus voltage 

via the 6-pole bridging connector. 

In total up to 4 switching actuator submodules can be 
connected in series to a switching actuator main module, 
so that a main module, if need be, can be extended sim-
ply from a 3-fold to a 6-, 9-, 12- or 15-fold switching 
actuator and thus be matched flexibly to the number of 
loads to be switched.  
It is indicated by flashing of the corresponding green LED 
A to E on the top of the main module if more sub-
modules are set than are actually connected or if the set 
submodule type does not correspond with the sub-
module type actually connected or if a submodule is 
detected as faulty. 
 

Behavior in case of mains failure / recovery 

Because the electronics of a submodule are fed from the 
bus (via the 6-pole interface to the main module), a 
mains failure then leads solely to a failure of the sub-
module if the bus voltage also fails as the result of a 
mains failure. However, it can be set for each submodule 

output individually which switching state it is to assume 
on a bus voltage failure and after the bus voltage recov-
ery: as before bus voltage failure, ON or OFF.

 

 

Application program 

The N 512/11 switching actuator needs the application 
program "07B0 A15 Switching Actuator 981B01". This 
controls the outputs of the main module as well as the 
outputs of all connected submodules via their 6-pole 
interface. 

 

In bus mode, a communication object can be available 
for each actuator output - for switching, for manual 
override, for a forced control, for a logical combination 
and for status query. Furthermore, if required, time-
limited switching instead of permanent switching on can 
be enabled for each channel via an optional "Night 
mode" object (e.g. for lighting while cleaning), if need be 
with a warning before switching off by multiple switch-
ing the output on and off (flashing). It can also be se-
lected whether all a module's outputs are to be set jointly 
and thus identically or whether each output is to be set 
separately and individually.

 

Amongst others, the application program includes op-
tional detection and monitoring  of  the  load  current  for 
each output on load failure and/or overload, simultane-
ous switching of all 3 outputs (3-phase switching), con-
version of a speed given as a percentage value into 1- to 
3-stage switching commands (fan speed control), con-
version of a valve setting given as a percentage value 
into a pulse width modulated (PWM) switching com-
mand (thermal drive control), a switching cycle and 
operating hours count with threshold monitoring for 
each output and an integrated 8-bit scene control, in 
which each output can be incorporated into up to 8 sce-
nes.

 

To load the application program, the Engineering Tool 
Software (ETS) is required as version 3.0 f or higher.

 

 

Note: If the N 512/11 application program is "unloaded" 

with the ETS, then you will no longer be able to activate 

direct mode, i.e. the LED status display and local switch-

ing of the outputs using the buttons on the front panel 

of the actuator are disabled. Only after reloading the 

application program can you re-enable the status display 

and direct mode. 

 

Summary of Contents for N 512/21

Page 1: ... each submodule output individually which switching state it is to assume on a bus voltage failure and after the bus voltage recov ery as before bus voltage failure ON or OFF Application program The N 512 11 switching actuator needs the application program 07B0 A15 Switching Actuator 981B01 This controls the outputs of the main module as well as the outputs of all connected submodules via their 6 ...

Page 2: ... data Power supply Bus voltage via the 6 pole bridging connector Bus current per submodule typically 1 mA Power dissipation if all outputs OFF 0 03 W at max load and all outputs ON approx 3 5 W Outputs 3 switching outputs potential free relay contacts rated voltage AC 230 400 V 50 60 Hz rated current 16 AX 200 µF to DIN EN 60669 1 16 A in AC1 mode cos ϕ 0 8 and in AC3 mode cos ϕ 0 45 as to DIN EN ...

Page 3: ...of protection according to EN 60529 IP 20 Overvoltage category according to IEC 60664 1 III Device complies with EN 50090 2 2 and EN 60669 2 1 EMC requirements Complies with EN 50090 2 2 EN 50428 and EN 60669 2 1 Environmental conditions Climatic withstand capability EN 50090 2 2 Ambient operating temperature 5 45 C Storage temperature 25 70 C Relative humidity not condensing 5 to 93 Markings none...

Page 4: ... the device Connecting a switching actuator submodule see figure 5 Snap the switching actuator submodule on to the rail and push it to the left against the switching actuator main module or against the switching actuator sub module Connect both devices using the bridging con nector supplied A B C Figure 5 Connecting a switching actuator submodule General notes Any faulty devices should be returned...

Reviews: