Hardware Installation
20
Building Technologies
048_DMS_NK8237_ICC_MP4.40_A6V10316241_a_en.doc
Fire Safety & Security Products
06.2011
5.2
NE8000 cabinets
5.2.1
NE8000 hardware requirements
Environmental requirements
The cabinets for NK8237 should always be installed in a clean and safe environ-
ment, away from dust, high temperature and humidity, vibrations and impacts.
Conditions and power supply should match the specific requirements given in the
Technical data section of the specific NK8000 datasheet.
NK8000 power requirements
Item
Power supply requirement
Input voltage
100-240 Vac, 50-60Hz
Input current
2A
A switch-box including a bipolar cut-out (phase + neutral) is required in the elec-
trical installation.
5.2.2
NE8000 hardware installation
Cabinet installation
The cabinet is typically wall-mounted. A proper support must be provided for the
maximum weight (see Technical data on the specific NK8000 datasheet). Four
supporting screws or hooks (min.10 mm) are required as shown in Fig. 12.
Supporting wall must not be composed of inflammable material.
Fig. 12 Cabinet installation
The VAC power supply wires (1.5 mm
2
) should be connected as illustrated in 0.
360 mm
415 mm