Configuration
48
Building Technologies
048_DMS_NK8237_ICC_MP4.40_A6V10316241_a_en.doc
Fire Safety & Security Products
06.2011
3.
In the browsing window that appears, define the location and name of the file,
and
click
Save
.
In a few moments, the CSV file is created.
For detailed information about the CSV file structure, refer to the NK8237 In-
terface Specifications guide (document no. A6V10316242).
Importing the address map
1.
Right click the
Modbus Master
node and select
Node Commands
.
2.
Select the
Import from CSV
command.
3.
In the browsing window that appears, locate the file to import and click
Open
.
In a few moments, the CSV file is imported and the address map updated.
A message on the screen indicates the correct execution of the import.