802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
159/293
Installation
Fig. 117: Protection ring
➭ Push the rubber sleeve onto the cable.
➭ Fit the cable T-plugs on the cable ends according to the manufacturer’s instructions.
➭ Mount the cable T-plugs one after the other on the phases L1 to L3 according to the
manufacturer’s instructions.
NOTE:
A too high torque can cause damage to the bushing. Tighten the cable plug
with a torque according to the manufacturer's instructions (max. 50 Nm).
Mounting the
arcing plate
After installation of the cable T-plugs of phases L1 to L3, one arcing plate each must be
mounted in the cable compartment. The arcing plates are fitted on the mounting plate below
the operating mechanism box (tightening torque for the arcing plates: 20 Nm).
The associated floor plate of the floor cover must be mounted after installation of a row of
cable T-plugs (see page 156, "Mounting the floor plates").
NOTICE
Flashovers due to insufficient electrical contact, abrasion or pollution of the push-on
surfaces (high-quality joints)
Will cause damage to the bushings in operation.
➭ All assembly work at the bushings must be carried out with particular care. Avoid
damaging the contact surfaces and the silicone surfaces.
➭ Avoid damage caused by the threaded stud while pushing on.
➭ Observe extreme cleanliness.
➭ No smoking.
NOTICE
Inappropriate installation of the plug sets
Damage to the plug sets due to thermal overloading.
If the electrical contact of the surfaces of the high-quality joints is insufficient, the plug sets can
overheat.
➭ The cable T-plugs must only be mounted by instructed personnel.
➭ Do not mount cable plugs in bent or twisted manner.
NOTICE
Removed protection ring
Will cause damages at the connection of the capacitive voltage detecting system.
A white plastic protection ring may be factory-assembled on the outside-cone bushing type C.
The protection ring serves as a stop for the plug, and protects the connection of the capacitive
voltage detecting system from damages when the cable plugs are mounted.
➭ Do not remove the protection ring.
INFORMATION