Operation
200/293
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Emergency operation of
the EARTHING function
If the switching device does not reach its end position, e.g. due to a failure of the auxiliary
voltage during earthing switch operation, push the operating lever with pushed-on adapter
onto the hexagonal shaft for the EARTHING function in such a way that the pin of the
hexagonal shaft fits in the inner slot of the operating adapter.
Fig. 166: Inserting the operating lever with pushed-on adapter (EARTHING function)
Switching operations
after emergency
operation
Perform further manual switching operations only with the associated operating lever for the
DISCONNECTING or EARTHING functions.
Initial situation
Push the interrogation lever downwards and hold it
Push the control gate to the left (the interrogation lever
locks in lower position. The actuating opening for the
EARTHING function opens)
To open the earthing switch, insert the operating lever
with pushed-on adapter and turn counter-clockwise
until the slots at the adapter are vertical to the
actuating opening (the position indicator is in OPEN
position)
Remove the operating lever with pushed-on adapter.
(The interrogation lever and the control gate return to
their initial position. the actuating opening closes)
End position
Remove the adapter from the operating lever and lay it
back into the service flap