Operation
248/293
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
7
➭ Push the interrogation lever downwards
again and hold it.
8
➭ Push the right-hand control gate to the left
and hold it (the interrogation lever locks in
lower position. The right-hand actuating
opening for the DISCONNECTING function
opens).
9
➭ Switch the right-hand three-position
disconnector to OPEN position (insert the
operating lever and turn 90° counter-
clockwise).
10
➭ Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).