802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
253/293
Operation
26.9
Operating bus sectionalizer panels with two three-position disconnectors
and with 900 mm panel width
Bus sectionalizer panel with two three-position disconnectors: Coupling the busbars
1
Initial situation
2
➭ Push the interrogation lever downwards and hold it.
3
➭ Push the control gate to the left and hold it (the interrogation lever
locks in lower position. The actuating opening for the
DISCONNECTING function opens).
4
➭ Switch the left-hand three-position disconnector to CLOSED position
(insert the operating lever and turn 180° clockwise).
5
➭ Remove the operating lever (the interrogation lever and the control
gate return to their initial position. The actuating opening closes).
6
➭ Push the interrogation lever downwards and hold it.