➭ Push the right-hand control gate to the left and hold it (the
interrogation lever locks in lower position. The actuating opening for
the DISCONNECTING function opens).
8
➭ Switch the right-hand three-position disconnector to CLOSED position
(insert the operating lever and turn 180° clockwise).
9
➭ Remove the operating lever (the interrogation lever and the control
gate return to their initial position. The actuating opening closes).
10
➭ To couple the busbars, close the circuit-breaker.