802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
259/293
Operation
5
➭ Remove the operating lever (the interrogation lever and the control
gate return to their initial position).
6
➭ Push the interrogation lever downwards again and hold it.
7
➭ Push the left-hand control gate to the right and hold it (the
interrogation lever locks in lower position. The left-hand actuating
opening for the READY-TO-EARTH function opens).
8
➭ Switch the left-hand three-position disconnector to READY-TO-EARTH
position (insert the operating lever and turn 180° clockwise).
9
➭ Remove the operating lever (the interrogation lever and the control
gate return to their initial position).
10
➭ To earth the right-hand busbar system, close the circuit-breaker.
11
➭ Fit a padlock.