Service information
276/293
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Necessary checks
Depending on the panel type, the checks listed in the following table must be executed:
29.1
Visual check at the operating mechanisms and the three-position switches
• Check galvanically plated surfaces for traces of corrosion.
• Check lubrication of sliding surfaces.
• Check firm seating of all terminal connections.
29.2
Visual check of spring-operated mechanism
Refers to panel types:
• Circuit-breaker panel (panel width 600 mm)
• Bus sectionalizer panel (panel width 600 mm)
• Disconnector panel (panel width 600 mm)
• Ring-main panel (panel width 600 mm)
• Vacuum contactor panel (panel width 600 mm)
• Metering panel (panel width 600 mm)
Panel type
Circuit
-
breaker panel Circuit-breaker panel
with 30,000 operating
cycles
Ring-main
panel
Bus sectionalizer
panel
Activity
Panel width [mm]
600
900
600
600
600
900
Check galvanically plated surfaces for traces of corrosion
X
X
X
X
X
X
Check lubrication of sliding surfaces
X
X
X
X
X
X
Check firm seating of all terminal connections
X
X
X
X
X
X
Check smooth operation of control gate and interrogation
lever
X
X
X
X
X
X
Visual check of spring-operated mechanism
X
-
-
X
X
-
Visual check of spring-operated/stored-energy mechanism
with fuse tripping
-
-
-
-
-
-
Visual check of slow motion mechanism
-
X
X
-
-
X
Visual check of circuit-breaker operating mechanism
X
X
X
-
-
-
Visual check of vacuum contactor operating mechanism
-
-
-
-
-
-
Check functionality and smooth operation of the cable
compartment interlock
X
X
X
X
X
X
Check fuse tripping
-
-
-
-
-
-
Panel type
Disconnector
panel
Vacuum
contactor
panel
Vacuum contactor
panel with fuse
assembly
Metering
panel
Switch-disconnector
panel with HV HRC
fuses
Activity
Panel width [mm]
600
900
600
600
600
600
Check galvanically plated surfaces for traces of corrosion
X
X
X
X
X
X
Check lubrication of sliding surfaces
X
X
X
X
X
X
Check firm seating of all terminal connections
X
X
X
X
X
X
Check smooth operation of control gate and interrogation
lever
X
X
X
X
X
X
Visual check of spring-operated mechanism
X
-
-
-
X
Visual check of spring-operated/stored-energy mechanism
with fuse tripping
-
-
-
-
-
X
Visual check of slow motion mechanism
-
X
-
-
-
-
Visual check of circuit-breaker operating mechanism
-
-
-
-
X
X
Visual check of vacuum contactor operating mechanism
-
-
X
X
-
-
Check functionality and smooth operation of the cable
compartment interlock
X
X
X
X
X
X
Check fuse tripping
-
-
-
X
X
X