Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Installation possibilities for cable connections and surge arresters, single-core PE- and XLPE-insulated
Circuit-breaker panel and disconnector panel 2000 A, 2500 A (panel spacing 900 mm)
Make
Conductor
cross-
section
1
In
su
la
ti
on
Cable T-plugs
Coupling inserts/
coupling plugs
Surge arresters with
According to
standard
[mm
2
]
bolted
bolted
Arresters
Coupling inserts
• GOST
(Russia, CIS)
• GB/DL (China)
12 kV
24 kV*
12 kV
24 kV*
additionally
2 cables per panel and phase
Nexans
Euromold
35…300
EPDM
2x 430TB/G
-
300SA-5(10)SA
-
IEC, GOST, GB/DL
2x K430TB/G*
-
300SA-5(10)SA
-
IEC
2x K430TB/G-CSxxx*
-
300SA-5(10)SA
-
GOST, GB/DL
35…300
EPDM
2x 480TB/G
-
800SA-10-xxx
-
IEC, GOST, GB/DL
2x K480TB/G*
-
800SA-10-xxx
-
IEC
50…630
EPDM
2x 484TB/G
-
800SA-10-xxx
-
IEC
35…630
2x K484TB/G*
-
800SA-10-xxx
-
IEC
Südkabel
50…300
Silicone 2x SET 12
-
MUT 23
-
IEC, GOST, GB/DL
25…240
2x SET 24*
-
MUT 23
-
IEC, GOST, GB/DL
300…500
Silicone 2x SEHDT 13
-
MUT 23
-
IEC, GOST, GB/DL
300…630
2x SEHDT 23*
-
MUT 23
-
IEC, GOST, GB/DL
nkt cables 25…300
Silicone 2x CB 12-630
-
CSA 12-x
-
IEC
25…500
2x CB 17.5-630
-
CSA 17.5-x
-
GOST, GB/DL
25…300
2x CB 24-630*
-
CSA 24-x
-
IEC, GOST, GB/DL
185…500
Silicone 2x CB 24-1250-2
-
CSA 12-x
-
IEC
95…500
2x CB 24-1250-2*
-
CSA 24-x
-
IEC
400…630
Silicone 2x CB 36-630(1250)
-
CSA 12-x
-
IEC, GOST, GB/DL
2x CB 36-630(1250)* -
CSA 24-x
-
IEC, GOST, GB/DL
Tyco
Electronics
Raychem
25…300
Silicone 2x RSTI-58xx
-
RSTI-CC-58SAxxxx
-
IEC
2x RSTI-58xx*
-
RSTI-CC-68SAxxxx
RSTI-SA-PIN
IEC
25…300
Silicone 2x RSTI-58xx-CEE01
-
RSTI-CC-58SAxxxx
-
GOST
2x RSTI-58xx-CEE01* -
RSTI-CC-68SAxxxx
RSTI-SA-PIN
GOST
400…800
Silicone 2x RSTI-395x
-
RSTI-CC-58SAxxxx
RSTI-SA-PIN
IEC
2x RSTI-595x*
-
RSTI-CC-68SAxxxx
RSTI-SA-PIN
IEC
400…800
Silicone 2x RSTI-595x-CEE01
-
RSTI-CC-58SAxxxx
RSTI-SA-PIN
GOST
2x RSTI-595x-CEE01* -
RSTI-CC-68SAxxxx
RSTI-SA-PIN
GOST
3M
50…240
Silicone 2x 93-EE 705-6
-
-
-
IEC, GOST, GB/DL
25…240
2x 93-EE 705-6*
-
-
-
IEC, GOST, GB/DL
300…400
Silicone 2x 93-EE 715-6
-
-
-
IEC, GOST, GB/DL
2x 93-EE 715-6*
-
-
-
IEC, GOST, GB/DL
GCA
35…500
Silicone 2x CJB10-630
-
-
-
GB
25…500
2x CJB20-630*
-
-
-
GB
ABB
Kabeldon
25…630
EPDM
2x CSE-A 12630-xx
-
-
-
IEC, GOST
2x CSE-A 24630-xx*
-
-
-
IEC, GOST
Cellpack
50…400
EPDM
2x CTS 630A 24kV
-
CTKSA
-
IEC
25…300
2x CTS 630A 24kV*
-
CTKSA
-
IEC
Ample
25…400
EPDM
2x AQT3-15/630
-
AHY5WZ7
-
GB/DL
35…500
2x AQT3-24/630*
-
AHY5WZ7
-
GB/DL
4 cables per panel and phase
Nexans
Euromold
35…300
EPDM
2x 430TB/G
2x 300PB/G
300SA-5(10)SA
-
IEC, GOST, GB/DL
2x K430TB/G*
2x K300PB/G*
300SA-5(10)SA
-
IEC
2x K430TB/G-CSxxx*
2x K300PB/G-CSxxx*
300SA-5(10)SA
-
GOST, GB/DL
35…300
EPDM
4x 480TB/G
2x 800PB/G
800SA-10-xxx
-
IEC, GOST, GB/DL
4x K480TB/G*
2x K800PB/G*
800SA-10-xxx
-
IEC
50…630
EPDM
2x 484TB/G
2x 804PB/G
800SA-10-xxx
-
IEC
35…630
2x K484TB/G*
2x K804PB/G*
800SA-10-xxx
-
IEC