Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
10.5
Motor protection table (with HV HRC fuses make SIBA)
20 … 23
1600
5 … 6
46.5
80
10 … 24
442
30 014 43.80
---
100
10 … 24
442
30 022 43,100
---
20 … 23
2000
5 … 6
57.8
100
10 … 24
442
30 022 43,100
---
System operating
voltage
Transformer
HV HRC fuse-link
U
n
[kV]
S
r
[kVA]
u
k
[%]
I
r
[A]
I
r
[A]
U
r
[kV]
e [mm] Order No. SIBA
Extension tube SIBA
U
n
System operating voltage
S
r
Rated power of transformer
u
k
Relative impedance voltage of transformer
I
r
Rated current of transformer
I
r
Rated current of fuse-link
U
r
Operating voltage / rated voltage of fuse-link
e
Dimension of fuse-link
Number of
starts per
hour
Maximum permissible motor starting current in A at rated normal current
of HV HRC fuse
40 A
50 A
63 A
80 A
100 A 125 A 160 A 200 A 224 A 250 A
3.3 - 7.2 kV
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
>7.2 - 12 kV Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
>12 - 23 kV
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
HV motors with
starting times up to 5
s
2
95
115
135
160
210
415
560
765
860
960
4
85
105
120
145
190
370
500
705
840
960
8
75
95
110
130
170
340
455
640
760
960
16
70
85
95
115
150
300
405
575
680
925
32
63
75
85
105
140
270
370
520
615
840
HV motors with
starting times up to
15 s
2
90
105
120
145
190
335
445
625
730
960
4
80
95
110
130
170
300
400
560
655
890
8
70
85
100
120
155
270
360
510
595
805
16
65
75
90
105
140
240
325
455
535
720
32
60
70
80
95
125
220
290
410
485
655
HV motors with
starting times up to
30 s
2
85
100
115
140
185
300
390
555
645
865
4
75
90
105
125
165
265
350
500
575
780
8
70
80
95
115
150
245
320
450
525
705
16
60
75
85
100
135
210
285
405
470
630
32
55
65
75
90
120
190
260
365
425
570