Installation
88/293
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Core drillings (incl. new plug systems)
Core drillings
• Circuit-breaker panel (panel width 450 mm, 630 A, 800 A)
Conductor distances
INFORMATION
For proper installation of the cable plugs, the following must be observed:
➭ Observe the specifications of the cable manufacturers.
➭ Drilling diameters depend on the cable cross-section.
①
1st cable
②
2nd cable
③
50...80 mm
Make
1st cable
2nd cable
Plug type
Distance [mm] Plug type
Distance [mm]
3M
93-EE 705-6
383
93-EE 718-6
275
Nexans Euromold
(K)400TB/G
383
- - -
- - -
(K)440TB/G
383
- - -
- - -
(K)430TB/G
383
(K)300PB/G
278
(K)480TB/G
383
(K)800PB/G
273
(K)484TB/G
383
(K)804PB/G
273
Südkabel
SET 12/24
383
SEHDK 13.1/23.1
273
nkt cables
CB xx-630
383
CB xx-630
283
CB 24-1250-2
383
CB 24-1250-2
283
CB 36-630(1250)
383
CB 36-630(1250)
273
Tyco Electronics Raychem
RSTI-L56xx
383
RSTI-CC-L56xx
283
RSTI-58xx
383
RSTI-CC-58xx
283
RSTI-x95x
383
- - -
- - -
GCA
CJBxx-630
383
CJBKxx-630
268
ABB Kabeldon
CSE-A xx630-xx
383
- - -
- - -
CSE-A xx630-03
383
- - -
- - -
Cellpack
CTS 630A 24kV
383
CTKS 630A 24kV
268
Ample
AQT3-15/630
383
AHT3-15/630
283
Solid-insulated bar
Moser-Glaser
372
- - -
- - -
Preissinger
- - -
- - -
Ritz
- - -
- - -