28 / 44
Siemens
VAV compact controller KNX/PL-Link G..B181.1E/KN
CE1P3547en
Building Technologies
2017-03-23
5.3.3 Min/max control by the VAV compact controller
When setting the minimum / maximum air volume flow in the VAV compact
controller, the supervisory controller must be set to V
min
= 0 % und V
max
= 100 %.
With this setting, the supervisory controller reference signal for both the supply air
and extract air controller is the same. Thus, supply air / extract air control with a
single reference signal is possible.
VAV ratio control 1 : 1
Supply air
Extract air
min
V
%
max
V
%
min
V
%
max
V
%
Supervisory controller
0 %
100 %
0 %
100 %
VAV compact controller
20 %
80 %
20 %
80 %
Reference signal: Y
supply_air
= Y
extract_air
= 25 %
Result:
V
supply_air
= V
extract_air
= 35 %
min
V
%
max
V
%
V
%
min
V
%
max
V
%
V
%
supply_ air
V
%
r
extract_ ai
V
%
Setting example B1