42 / 44
Siemens
VAV compact controller KNX/PL-Link G..B181.1E/KN
CE1P3547en
Building Technologies
2017-03-23
9.2 Device parameters (ACS931 / ACS941 /
AST20)
Designation
Setting
Factory setting
Can be set with
Maximum air volume flow (Vmax) 20...120 %
100 %
ACS931, ACS941, AST20
Minimum air volume flow (Vmin)
-20...100 %
0 %
ACS931, ACS941, AST20
Opening direction (DIR)
r or L
r
ACS931, ACS941, AST20
Adaptive positioning (ADP)
Off or on
Off
ACS931, ACS941
Nominal air volume flow (Vnom)
0 …. 65’535 m
3
/h 0
m
3
/h
ACS931, ACS941
Elevation above sea level
0…5000 m
(in 500 m steps)
500 m
ACS931, ACS941
Running time
30 … 150 s
150 s
ACS931, ACS941
Vn
1.00 ... 3.16
1.00
ACS931
9.3 Parameters for engineering tools
ETS = ETS3 or ETS4.0.6 (or newer); ACS = ACS790 version 8.00 or newer
Designation
Setting
Factory setting
Can be set with
Nominal volume flow
0…214’000 m
3
/h
100 m
3
/h
ETS, ACS, ABT
Hysteresis volume flow
1…214’000 m
3
/h
1 m
3
/h
ETS, ACS, ABT
Min. repetition time volume flow
10 s … 900 s
10 s
ETS, ACS, ABT
Minimum volume flow
-20…100 %
0 %
ETS, ACS, ABT
Maximum volume flow
20 …120 %
100 %
ETS, ACS, ABT
Elevation above sea level
0…5000 m
(in 500 m steps)
500 m
ETS, ACS, ABT
Opening direction
CW / CCW
CW
ETS, ACS, ABT
Adaptive positioning
On / off
Off
ETS, ACS, ABT
Backup mode
Backup value, Keep
last state
Backup value
ETS, ACS, ABT
Backup position
0…100 %
0 %
ETS, ACS, ABT
VAV operating mode
Volume flow control
Position control
Volume flow
control
ETS
Type of air
Outside air,
Primary supply air,
Supply air,
Extract air
Outside air
ACS
Master/Slave
Autonomous,
Master,
Slave
Autonomous
ACS