43 / 44
Siemens
VAV compact controller KNX/PL-Link G..B181.1E/KN
CE1P3547en
Building Technologies
2017-03-23
9.4 S-mode
datapoints
Nr.
Name in ETS
Object
function
Flags
Data point type KNX
Range
C R W T
U ID
DPT_Name
Format
Unit
1
Fault information
Transmit
1 1 0 1 0 219.001 _AlarmInfo
6
Byte ---
[0...255 ] = Log Nr.
[0...2] = Alarm priority
[0...14] = Application area
[0...4] = Error class
[0...7] = Attributes
[0...7] = Alarm status
2
Fault state
Transmit
1 1 0 1 0 1.005
_Alarm
1 bit
---
0 = No alarm
1 = Alarm
3
Fault
transmission Receive
1 0 1 0 1 1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
4
Setpoint
Receive
1 1 1 0 1 5.001
_Scaling
1
Byte %
0..100%
5
Damper position
Transmit
1 1 0 1 0 5.001
_ Scaling
1
Byte %
0..100%
6
Volume flow
relative
2)
Transmit
1 1 0 1 0 5.001
_ Scaling
1
Byte %
0..100%
Transmit
1 1 0 1 0 8.010
_Percent_V16
2 Bytes %
-327.68..327.67%
Transmit
1 1 0 1 0 5.004
_ Percent_U8
1
Byte %
0..255%
7
Volume flow
absolute
2)
Transmit
1 1 0 1 0 9.009
_Value_Airflow
2 Bytes m
3
/h -670 760..670 760 m3/h
Transmit
1 1 0 1 0 14.077 _
Volume_Flux
4 Bytes m
3
/s 0..(2
32
-1)
8
Fault
Transmit
1 1 0 1 0 1.005
_Alarm
1 bit
---
0 = No alarm
1 = Alarm
9
Overridden
Transmit
1 1 0 1 0 1.002
_Bool
1 bit
---
0 = False
1 = True
10 Override
position
1 Receive
1 1 1 0 1 1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
11 Override
position
2 Receive
1 1 1 0 1 1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
12 Balancing
mode
Receive
1 1 1 0 0 1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
13
Vmin
5)
Receive
1 1 1 0 1 8.010
_Percent_V16
2 Bytes %
-327.68..327.67%
14
Vmax
5)
Receive
1 1 1 0 1 8.010
_Percent_V16
2 Bytes %
-327.68..327.67%
15 Vnom
Read-only 1 1 0 0 0 9.009
_Value_Airflow
2 Bytes m3/h -670 760..670 760 m3/h
16 Opening
direction Read-only 1 1 0 0 0 1.012
_Invert
1 bit
---
0 = Not Inverted
1 = Inverted
17
Diff. pressure
6)
Read-only 1 1 0 0 0 9.006
_Value_Pres
2 Bytes Pa
0..670 760 Pa
Read-only 1 1 0 0 0 14.058 _Value_Pressure 4
Bytes Pa
0..(2
32
-1)
18 Coefficient
Read-only 1 1 0 0 0 14.*
4-Byte Float
4 Bytes ---
0..3.16
19 OEM-Reset
Receive
1 0 1 0 0 1.017
_Trigger
1 bit
---
0, 1 = Trigger
5)
For technical reasons, values for Vmin / Vmax need to be entered with two trailing “0” in ETS5, i.e. to get Vmin = 5%, enter
“500%” in ETS5. The same applies for read-back values.
6)
For some group objects, alternative data point types (DPT) can be selected in ETS. The first entry indicates the default setting.