background image

 

 

Installation Instructions

Document No. 129-367

September 1, 2003

OpenAir™ Electronic Damper Actuator 
GDE/GLB Rotary Non-spring Return  

 

b

e

d

f

a

45

 

90  

90  

EA0678R3

c

 

a. Actuator 
b. Position 

indicator 

c. Mounting 

bracket 

d. Mounting 

screws 

e.  4 mm hex key 
f.  Shaft insert for use with 

3/8-inch (8-10 mm) shafts

 

Figure 1. Parts of the GDE/GLB Rotary Actuator. 

Product Description 

Steps for direct-coupled mounting of the OpenAir 
GDE/GLB Series non-spring return rotary electronic 
damper actuator. 

Product Numbers 

GDE131.1U GLB131.1P 
GDE131.1U/B (24 pk)  

GLB132.1P 

GDE131.1P GLB136.1P 
GDE131.1P/B (24 pk) 

GLB161.1P 

GDE131.1Q/B 6-ft cable (12 pk) 

GLB163.1P 

GDE132.1P GLB164.1P 
GDE136.1P  

GLB166.1P 

GDE161.1P  
GDE161.1P/B (24 pk) 

 

GDE163.1P  
GDE164.1P  
GDE166.1P  

 

Required Tools 

• 

4 mm hex wrench 

• 

4 mm (5/32-inch) drill bit and drill 

• 

Small flat-blade screwdriver 

• 

Marker or pencil 

Estimated Installation Time 

30 minutes  

Warning/Caution Notations 

WARNING

 

Personal injury/loss of life may 
occur if you do not follow a 
procedure as specified. 

CAUTION: 

 

Equipment damage or loss of 
data may occur if you do not 
follow a procedure as 
specified. 

 

Instructions 

 

WARNING: 

Do not open the actuator. 

NOTE: 

Place the actuator on the damper shaft so 
that the front of the actuator is accessible. 
The label is on the front side.  

1.  Determine whether the damper blades will rotate 

clockwise or counterclockwise to open. See  
Figure 2. 

2.  If the blades will rotate counterclockwise, slide the 

manual override switch to manual, and move the 
adjustment lever to the right. Return the switch to 
automatic. See Figure 9. 

 

To mount a (modulating) GDE/GLB16x, set the Dual 
In-line Package (DIP) switches to the required 
positions. 

1.  To access the DIP switches, raise the tab on the 

lower left side of the actuator. See Figure 2. The 
factory setting is clockwise (middle switch), with a 
direct-acting feedback signal (right switch). 

2.  Close the tab over the DIPswitches. 

To mount a (3-positon) GDE/GLB13x for counter-
clockwise rotation, follow the 

Counterclockwise 

Damper Rotation

 instructions located in the 

Wiring

 

Diagrams

 section when wiring the actuator to the 

controller. 

 

Item Number: 129-367, Rev. 010

 

Page 1 of 6 

Summary of Contents for OpenAir GDE131.1P

Page 1: ...you do not follow a procedure as specified CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Instructions WARNING Do not open the actuator NOTE Place the actuator on the damper shaft so that the front of the actuator is accessible The label is on the front side 1 Determine whether the damper blades will rotate clockwise or counterclockwise to open See...

Page 2: ...nstalled 1 2 inch guide See Figure 3 EA0999R1 Figure 3 Removing 1 2 inch Ø shaft guide for 3 8 in or 5 8 in shaft 45 90 90 EA0679R3 f Mounting GDE GLB on 3 8 inch 8 10 mm shafts Figure 4 3 8 Ø inch shaft see Figure 1 Item f 1 A 3 8 inch shaft adapter is provided in actuator package 2 Hold the shaft insert so that the raised tabs are inserted last when placing the insert into the back of the actuat...

Page 3: ... of the points to the setting Manually turn the red ring of the B switch The narrower tab on the ring points to the setting See Figure 10 The auxiliary switch setting shafts rotate with the actuator NOTE The scale is valid only when the actuator is in the 0 position on clockwise motion 80 70 60 20 10 AUX SWITCH ADJUSTMENT A B 50 EA0636R2 Figure 10 Auxiliary Switch Setting Dial Mechanical Range Adj...

Page 4: ...iring must conform to NEC and local codes and regulations Use earth ground isolating step down Class 2 transformers Do not use autotransformers Determine the supply transformer rating by summing total VA of all actuators used It is recommended that one transformer power no more than 10 actuators WARNING Installations requiring Conformance All wiring for CE rated actuators must only be separated ex...

Page 5: ...position control Each wire has the standard symbol printed on it See Table 1 M A B 1000 P1 P3 P2 S1 S4 S2 S3 S5 S6 1 6 7 EA0282R1 EA0635R2 24 Vac EARTH GROUND ISOLATING CLASS 2 TRANSFORMER FOR 24 Vac POWER SAFETY ISOLATING TRANSFORMER PER EN 60742 120 Vac 7 ORANGE 6 VIOLET 1 RED NEUT Figure 14 3 position Control GDE GLB16x 24 Vac power supply 0 to 10V modulating control Each wire has the standard ...

Page 6: ...88P25 OpenAir Electronic Damper Actuators GDE GLB Series Non spring Return Rotary 24 Vac Three Position Control Information in this publication is based on current specifications The company reserves the right to make changes in specifications and models as design improvements are introduced OpenAir is a trademark of Siemens Building Technologies Inc Other product or company names mentioned herein...

Reviews: