Data point
Explanation, example
Message receiver 1…4
Default val: (Blank)
Setting val: Max. 20 char.
·
Message receiver 1…4 is a name (text)
and is displayed in the web browser. You
must run "generate" to display the change
(for the workflow, see Section "Refresh
device web pages" in Section 2.4)..
—
Receiver type
Default val: ---
Setting val: ---, E-mail
The following recipient types are available:
---
: No messages to this recipient.
: Message recipient configured for e-
mail messages via Ethernet.
—
Fault priority
Default val: All
Setting val: All,
Only urgent ones
Setting value "
Only urgent ones
" serves as a
filter when sending system reports and fault
status messages.
—
E-mail address
Default val: messagereceiver@
Setting val: Max. 46 characters
For E-mail recipient types:
Setting value is recipient email address.
—
The number of messages pending is available under "Number of messages for
sending".
A time frame can be defined during which messages can be sent for each receiver.
·
The following settings are optional when restricting the time for sending
messages (default settings: No restriction).
·
In general: Messages occurring outside the send periods are sent afterwards if
still pending during the send period.
Path: Home > 0.5 OZW672… > Message receiver > Message receiver 1…4 >
Send messages
You can define time periods per weekday or special day when messages can be
sent to the message receivers.
Special days are defined via
Holidays/special days
.
Data point
Explanation, example
Monday...Sunday,
Special day
Default val: Monday
00:00 On …
Special day
00:00 On …
Setting
val: Monday...Sunday,
Special day
00:00…24:00
Off / On
Max 3 sending periods can be defined when
Web Servers can send messages for each
weekday and special day(s). The previous
day's status is transferred to the current day.
The default settings is to always send
messages.
Send messages
Notes