127 / 143
Siemens
Web Server OZW672... V6.0
CE1C5712en
Building Technologies
Appendix
2015-10-13
9 Appendix
9.1 General
notes
Names of data points and message text, e.g. of faults, cannot contain special
characters or umlauts. Valid characters:
·
a…z and A…Z
·
0…9
·
! „ $ % & ‚ ( ) * + ` - . / : ; < = > ? "Space
When sent,
invalid characters
will be converted to "
?
" (question marks).
9.2 Diagnostics
9.2.1 Web Server fault codes
Fault code
Web Server fault
General
0
No fault
Communications
81
No bus power supply
1)
95
Invalid time of day (Web Server time not or incorrectly entered).
100
>1 clock time master
142
Device failure (Bus)
2)
171
[Fault input 1] fault
172
[Fault input 2] fault
438
Incorrect bus connected
439
Bus module not identified
448
Message receiver 1 not reached
3)
449
Message receiver 2 not reached
3)
450
Message receiver 3 not reached
3)
451
Message receiver 4 not reached
3)
486
Energy ind. receiver 1 not reached
487
Energy ind. receiver 2 not reached
512
Trend receiver 1 not reached
513
Trend receiver 2 not reached
System configuration errors
82
>1 identical device address
(Devices have same address).
514
Change local Admin'password
1) Device failure monitoring (Bus) is stopped if the bus has no power.
2) Created by the Web Server for the device failed.
Device failure (Bus) as a result, device failure (bus) is assigned to "System faults",
whereas all other faults generated by the Web Server are assigned as "Local faults".
3) Possible causes of recipient type e-mail: Erroneous Ethernet or e-mail settings.
Text entry
Note
Fault codes