43 / 176
Siemens
Web server OZW772... V6.0
CE1C5701en
Building Technologies
Commissioning
2015-10-12
2.10 Supply state
The Web Server can be reset to factory default settings. This is probably a good
idea when using the Web Server for another plant.
Procedure:
1. Simultaneously press "Long" (> 6 seconds) on the "Remote"
button
and "Prog"
The LED "On"
turns off. The Web Server restarts.
2. Wait until the Web Server is operational (LED "Run"
is green).
When restoring default state:
·
All settings are reset to default state.
·
Plant diagrams are deleted.
·
The device list is deleted.
·
Uploaded files are deleted.
·
Unsent messages are deleted.
·
History data is
not
deleted:
It must be deleted manually (see Section 2.8).
The KNX device addresses and Ethernet IP address are also reset to default state.
2.11 Software updates
We differentiate between the following:
·
System definition updates to integrate device descriptions of new devices in the
Web Server.
·
Firmware updates to update the Web Server to the latest firmware version.
Firmware updates may also contain new device descriptions (system
definitions).
The Web Server supports a number of Synco devices and differentiates them via
device descriptions. A text catalog with various languages contains all Web Server
texts and device descriptions.
A system definition update is a simply operational step via web browser.
See Section 4.4 for information on uploading system definitions.
The current, installed version of system definitions is displayed in device info.
Local operation on Web Server required to update firmware. Procedures are
communicated for any firmware update accordingly.
The logos can be customized.
Restore default state
Note
Note
System data update
Note
Firmware update
Logo update