You can consult the following information as needed to analyze problems on the
Ethernet. It displays the current settings for the subnet.
The Ethernet settings are made in Section 2.5.3, Operating page "Settings".
Path: Home > 0.2.150 OZW772.xx > Device information > Ethernet.
Data point
Explanation, example
DHCP client
Displays whether the DHCP client is switched
on.
IP address
Web Server IP address. The factory IP address
for the Web Server on the Ethernet is:
192.168.2.10
Subnet mask
The subnet mask defines the size of the subnet.
A value of 255 masks the partial network; a
value of 0 masks the device portion of the IP
addresses on the subnet. Devices must have
the same partial network to communicate
directly.
The Web Server has a default subnet mask
255.255.255.0
Default gateway
The standard gateway connects the subnet for
the Web Server to additional networks, e.g. the
Internet. The router typically is the default
gateway.
Preferred DNS server
Preferred DNS server required to send e-mails.
The router is typically the DNS server as well for
the Web Server.
Alternate DNS server
An alternative DNS server is only defined for
redundant systems and is typically empty.
Physical address
The physical address (MAC address) is a
unique identification for the Ethernet interface.
Alternative settings are used for the following when the DHCP client is switched off:
·
IP address
·
Subnetmask
·
Standard gateway
·
Preferred DNS server
·
Alternative DNS server
Setting for DHCP client