2.5.2 Operating page "Faults current"
Local faults and faults in system are displayed under "Faults current".
Path: Home > 0.5 OZW672… > Faults current
A description of faults is available in Section 4.3,"Faults"
2.5.3 Operating page "Settings"
2.5.3.1 Web
Server
Path: Home > 0.2.150 OZW772.xx > Settings > Web Server
Data point
Explanation, example
Language
Default val: English
Setting val: see example
Web Server language: Is used for Web Server
fault texts, message history, messages and
system reports.
—
Code
Default val: 01
Setting val: max. 20 charact.
Access code for PC Software ACS790.
—
Reset admin password *
Default val: No
Setting val: Yes
If you do not know the administrator password
for the Web Server, setting value "Yes" again
provides access to the Web Server via the
administrator password "Password".
"Password or Password.1" is possible again
(Administrator password for delivery of
devices to Version 5.2 = "Password", for
devices as of Version 6.0 = "Password.1").
Setting value "Yes" is a temporary state, i.e.
the setting value automatically goes to "No"
after ca. 2 seconds.
*
—
*
—
* with PC software ACS790 only.
2.5.3.2 Time of day/date
Path: Home > 0.2.150 OZW772.xx > Settings > Time of day/date
Data point
Explanation, example
Time zone
Default val: GMT +01:00
Berlin, Rome
Setting val: misc. Time zones
The time zone setting value is based on UTC
(GMT). The time zone also defines daylight
saving time / standard time changeover.
—