background image

Installation Instructions

The following instructions are for the installation of a Siemens JD main breaker kit in a 400 amp Revised P1 Panel-

board.  The parts provided in this kit are for connection to a 1-phase 2 or 3-wire system or to a 3-phase 3 or 4-wire 

system.  For all 1-phase systems, disregard the B-phase connector instructions.  The breaker is NOT included with 

this kit and must be purchased separately.   Be sure to choose the appropriate breaker for the voltage, system & 

feed location in use.  For systems with no neutrals, disregard the neutral connection.

NOTE:  Other main breaker kits may include this kit AND a breaker with main breaker support(s) attached.   

White text on black background on these pages denote instructions specific to these particular kits (see 

list on front cover).  (For clarification, DANGER warning below applies to all.)

11-A-1115-01 Rev. 02

-3-

-2-

DANGER

Hazardous voltage.

Will cause death or

serious injury.

Keep out.

Qualified personnel only.

Disconnect and lock off all

power before working on 

this equipment.

11.  Attach the main cables to the breaker and neutral

       terminal and torque connections to values specified

       on the device.  If no values are listed on the device, 

       refer to the Hardware Tightening Torque label

       affixed to the rear of the deadfront.

8.  On 1-phase 3-wire and 3-phase 4-wire systems,

     neutral lugs are required.  For the 600 kcmil neutral 

     lug (item 11), insert the 1/4”-20 x 1” carriage bolt 

     (item 13) through the square hole on the neutral

     riser from below, then place the 600 kcmil neutral 

     lug and the anti-turn plate (item 12) as shown.  

     Finish with the 1/4”-20 belleville washer nut (item 14).

14.  Before energizing the panel, ensure that all con-

       nections have been properly torqued, that all 

       circuit breaker terminal covers are secured, that the 

       deadfront is installed and that all fillers are in place.

BREAKER SUPPORT BARRIER

1

PHASE CONNECTOR

BREAKER ESCUTCHEON

MAIN LABEL

3/8” NARROW WASHER

HELICAL SPRING LOCKWASHER

DEADFRONT

DEADFRONT

SUPPORT

BASE

RAIL

NEUTRAL

CROSS BUS

** (2) FOR 1Ø, (3) FOR 3Ø

NEUTRAL

CROSS BUS

**

**

**

1

1

MAIN

END

FEED-THRU

OR SUBFEED

END

1

2

3

4

5

6

7

3/8”-16 x 1” HEX HEAD BOLT

5/16”-18 x 3/4” HEX HEAD SEMS* ASSEMBLY SCREW

***

2

**

8

9

1/4”-20 x 2-3/4” PHILLIPS ROUND HEAD THREAD-FORMING SCREW

5.  Position one of the outer breaker connectors

     (item 2) so that the single-hole end rests on the

     breaker pad and the double-hole end rests on

     the panel section or main bus.  Note that the

     outer connectors are mirror images and are NOT

     interchangeable.  Attach the connector to the 

     breaker pad using 3/8”-16 bolt (item 7), a helical

     spring lockwasher (item 6) and a plain washer

     (item 5) as shown.  Do not tighten at this time.

     Repeat the process to attach the other outer

     connector to the breaker. 

6.  3-Phase panels require a B-phase connection.

     Position the B-phase connector so that the single-

     hole end rests on the breaker pad and the double-

     hole end rests on the panel section or main bus.  

     Attach the connector to the breaker pad using 

     the same hardware as the A and C-phases.  

     Do NOT tighten at this time. 

10.  Torque all connections to the values specified on

       the Hardware Tightening Torque label affixed to the

       rear of the deadfront (or reference assembly instructions

       where appropriate).

* SEMS ASSEMBLY SCREWS HAVE A CAPTIVE WASHER ON THE SCREW

THIS KIT CONTAINS THE FOLLOWING ITEMS:

ITEM

QTY

DESCRIPTION

4

9

MAIN

OPENING

3

2

BREAKER

SUPPORT

BRACKET

350 kcmil NEUTRAL LUG ASSEMBLY

600 kcmil NEUTRAL LUG

1

1

10

11

12

ANTI-TURN PLATE

1/4”-20 x 1” CARRIAGE BOLT

1

2

1

13

14

1/4”-20 BELLEVILLE WASHER NUT

*** (4) FOR 1Ø, (6) FOR 3Ø

1

5

6

7

8

11

10

14

12

13

4.  Refer to Figure 2 on page 4 to determine the

     correct breaker mounting for the panel’s feed

     location.  Also refer to main breaker instructions

     for access to mounting holes; breaker covers

     may need to be removed for access.  Follow

     instructions on the Wire Grip Kit Installation

     Instructions to install breaker lugs (lug kit

     TA2J6500; purchased separately) on the 

     correct end of the breaker before continuing.
     

TOP FEED: 

 Install lugs at the ON end of the breaker.

    

 

The breaker support bracket is pre-installed on

     the breaker ON end.  Attach this bracket to the 

     base rails using the hardware removed in step 3.

     Skip to step 5.

  

     

BOTTOM FEED: 

 Install lugs at the OFF end of 

     the breaker.  

    

 

Leave the pre-installed breaker support bracket

     attached to the breaker but note it does not need

     to be secured to the base rails.  Instead, attach

     the breaker to the existing mounted support 

     bracket (as shown in Fig. 2A on pg. 4) by 

     following these directions:

     

     Insert both 1/4”-20 x 2-3/4” screws (item 9) through

     the appropriate end of the breaker case and through

     the outer holes on the support barrier (item 1) 

     as shown in Figure 1, to retain the barrier during

     installation.  Fasten the breaker to the support.

Figure 1

7.  Fasten all breaker connectors to the panel section

     or main bus using two 5/16”-18 SEMS screws 

     (item 8) per joint.  

12.  Remove the main lug blank filler from the deadfront

       main opening (if present).  Refer again to Figure 3

       on page 4 to determine the correct orientation of the

       deadfront main breaker escutcheon (item 3) for the 

       panel’s feed location.  Insert the breaker escutcheon

       into the front of the deadfront.  
13.  For main breaker applications, apply the “MAIN”

       label (item 4) to the breaker escutcheon as shown.

For installation as a Main Breaker:

1.  Lock off all power supplying this equipment

     before working on it.

3.  To install this kit for main breaker use, remove

     the main lugs (if installed).  
     

TOP FEED:  Also remove the main breaker 

     support already installed onto rails.  (Save

     hardware for mounting of pre-installed support.) 

2.  Remove the deadfront.

9.  Position the 350 kcmil neutral lug assembly (item 10)

     under the neutral riser, allowing the stud to pene-

     trate as shown.  Fasten it to the riser with a 1/4”-20

     belleville washer nut (item 14). 

 

     NOTE:  

If the panelboard is fed by two 250 kcmil

     or smaller cables, this lug assembly is used for the 

     second incoming cable and one of the 1/0 terminations

     on the neutral strip is used for a grounding electrode

     conductor (if required for service equipment appli-

     cations).  If the panelboard uses a 600 kcmil cable 

     for neutral and is being used as service equipment,

     the 350 kcmil lug is used for the grounding electrode

     conductor. 

N/A

N/A

N/A

72 lb-in

TORQUE

N/A

N/A

N/A

72 lb-in

N/A

N/A

N/A

N/A

****

240 lb-in

**** TORQUE (lb-in):  72 for 1/8” CU; 108 for 3/16” or 1/4” AL; 144 for 3/16” CU

Bottom-feed mains are reverse fed, 

and require Type JXD breakers.  

Top-feed mains may be either 

Type JD or JXD:

Top-feed Main Breakers:

JD, HJD, JXD, HJXD

Bottom-feed Main Breakers:

JXD, HJXD

The P1-400 Panel provides wiring

space for the following cable options:
For (2) 250 MCM line cables per 

phase use breaker line lug 

TA2J6500

or copper lug 

TC2J6500

For (1) 600 MCM line cables per 

phase use breaker line lug 

TA1L6750

 

or copper lug 

TC1J6600

NOTE:  Kits that include a breaker will have the following

items pre-assembled to the breaker and are not included

in the itemized list on this page:

(1) Type JD circuit breaker

(1) breaker support barrier (see item 1)

(2) 1/4”-20 round head screws (see item 9) 

(1) breaker support bracket

(All items in the itemized list below are included in this kit

 for use as needed for installation per these instructions.)

Reviews: