Before soldering the valve into the pipework, the flow
direction must be carefully checked
•
Make sure that all soldering material, copper grindings etc.
are removed from the pipework
•
The valve body must be cooled with a wet cloth during the
soldering
•
Mount a filter upstream to the valve
m
in
.
5
0
m
m
/
2
in
3371
Z
22
•
The pipework must be fixed so that the valve connection
supports do not come under any mechanical load.
Vibrations can lead to pipework breaking!
•
Evaporator temperature below 0 °C:
the valve body (incl.top/signal converter)and pipework
leading away from the valve must be isolated
•
Evaporator temperature above 0 °C:
only the valve body and the pipes leading away from the
valve must be isolated (see picture).
Do not isolate upper part and electronics (overheating)!
33
7
1Z
23
Pressure sensor
•
Pressure sensor must be mounted upright over the
pipework
•
Can be mounted directly on the suction pipe
Temperature sensor
135°
337
1Z
07
•
Mount as near as possible to the
evaporator outlet (max. distance 2 m /
6.5 ft) on a straight piece of pipework /
inmediately after or on the outside part
of an elbow
•
Fix with a cable tie
•
Isolate
Note
The further the sensor is from the evaporator, the more
stable the control (max. 2 m).
It is recommended to increase the setpoint of superheat
accordingly.
30/124
Building Technologies
CPS40
CE1U3372XX / H 74 319 0555 0 a
HVAC Products
22.09.2006
Summary of Contents for PolyCool CPS 40
Page 26: ...26 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Page 50: ...50 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Page 74: ...74 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Page 98: ...98 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...