Polygyr

®

-Compact

Technical Instructions

Document No. CM1N3407E-P25

Rev. 1, February, 2000

Discharge Air Temperature
Controller

Siemens Building Technologies, Inc.

Features

 

Two outputs for heating and cooling

 

Continuous control signal

 PI 

control

 Electronic

 24 

Vac

Application

The RCM61.22 is used for controlling discharge air temperature in smaller ventilating
and air conditioning installations (by heating and cooling).

Application examples:

 

Individual installations, (kitchens, cloak rooms, storage rooms, etc.)

 

Zone control in larger installations

The following units can be controlled:

 

Heating and cooling valve actuator

 

Air damper actuator

 

Step controller or current valve for electric air heater battery

 

Signal converter

The temperature controlled by the RCM61.22 can be shifted:

 

by the outdoor temperature to obtain summer/winter compensation.

 

by a building automation system to obtain set point adjustment (fixed value shift).

Product Number

RCM61.22

Ordering

When ordering, specify quantity, product number and description.

Summary of Contents for Polygyr-Compact

Page 1: ...d cooling Application examples Individual installations kitchens cloak rooms storage rooms etc Zone control in larger installations The following units can be controlled Heating and cooling valve actuator Air damper actuator Step controller or current valve for electric air heater battery Signal converter The temperature controlled by the RCM61 22 can be shifted by the outdoor temperature to obtai...

Page 2: ...tes a control signal of 0 10 Vdc The outputs are switched in sequence and their mode of operation is opposed making it possible to provide sequence control of two actuators with different modes of operation Y Q Q Y Load Signal voltage Heating Cooling 0 10V SASC0016R1 0 Figure 1 Compensation The reference value is fed to the controller which shifts the set point There are two possibilities Universa...

Page 3: ...an be bent and adapted to the shape of the duct It senses the average temperature in the duct because the measuring element Ni wire extends over the total length of the flexible sensing element Unit Combinations The RCM61 22 can control various units with the following characteristics Type of control 10 Vdc Operating voltage 24 Vac Remote Setting Units The FZA21 11 remote setting unit is used for ...

Page 4: ...he supply air fan if the latte is mounted after the last air handling unit Otherwise after the air handling unit with a clearance of at least 1 64 feet The flexible sensing element should be positioned diagonally in the duct but must not come in contact with the duct wall Installation Instructions are supplied with the unit Commissioning The wiring must be checked when commissioning the installati...

Page 5: ...her switching functions which can vary from one installation to another according to the operating conditions SP SN 24V Y1 R M Z1 Z3 G Y1 G Y R M U G0 Y2 Y2 G Y R M U G0 N1 G0 SASC0018R1 R R1 M N1 RCM61 22 Discharge Air Temperature Controller R1 FZA21 11 Remote Setting Unit Y1 Actuator for heating Y2 Actuator for cooling Figure 3 Exhaust Air Temperature Control with Low Limiting of Discharge Air T...

Reviews: