Appendix
Object list
10
62 | 70
A6V11471220_en--_e
393
1
17
UFS -
User
Fan
Speed
Setting
Interface
Object type
1
1
U16 /
PDT_UNSIGNE
D_INT
R
----
Fan Speed user's
setting
ObjectIndex
29 1
U8 /
PDT_UNSIGNE
D_CHAR
U8 /
DPT_Value_1_
Ucount
R
Rea
d.ind
needed for Object
Index Discovery via
LTE-Read onto this
Property
=> SD-
T060.0601_EN_SARB
_Data_Aquisition:
7.1.2.10.1
KNX Standard,
chapter 3-5-1,
PID_OBJECT_INDEX
FanBoostRe
q
16
2
1
B1 /
PDT_BINARY_I
NFORMATION
R
IR.re
q
FanBoostReq refers to
the optional process
output property of AB
UFS representing a
trigger command
requested by the room
occupant to initiate the
temporary Fan Boost
fan mode in HRV
applications
=> cASA-[T022.S035-
2I055] Fan operation:
Fan Boost/Fire
Place/Kitchen Hood
FirePlaceRe
q
16
3
1
B1 /
PDT_BINARY_I
NFORMATION
R
IR.re
q
FirePlaceReq refers to
the optional process
output property of AB
UFS representing a
trigger command
requested by the room
occupant to initiate the
temporary Fire Place
fan mode in HRV
applications.
=> cASA-[T022.S035-
2I055] Fan operation:
Fan Boost/Fire
Place/Kitchen Hood
KitchenHood
Req
16
4
1
B1 /
PDT_BINARY_I
NFORMATION
R
IR.re
q
KitchenHoodReq
refers to the optional
process output
property of AB UFS
representing a trigger
command requested
by the room occupant
to initiate the
temporary Kitchen
Hood fan mode in
HRV applications.
=> cASA-[T022.S035-
2I055] Fan operation:
Fan Boost/Fire
Place/Kitchen Hood
ResetTmpFa
nReq
16
5
1
B1 /
PDT_BINARY_I
NFORMATION
R
IR.re
q
ResetTmpFanReq
refers to the optional
process output
property of AB UFS
representing a trigger
command requested
by the room occupant
to cancel an activated
temporary fan mode in
HRV applications.
=> cASA-[T022.S035-
2I055] Fan operation:
Fan Boost/Fire
Place/Kitchen Hood
FanBoostPro
longTime
16
6
1
U16 /
PDT_UNSIGNE
D_INT
R
IR.re
q
FanBoostProlongTime
refers to the optional
process output
property of AB UFS to
adjust the duration of
the temporary Fan
Boost ventilation mode
in HRV applications.
=> [T022.S035-
2I058.020] Operation
of ‘Fan Boost’, ‘Fire
Place’ prolong time
settings
FirePlaceProl
ongTime
16
7
1
U16 /
PDT_UNSIGNE
D_INT
R
IR.re
q
FirePlaceProlongTime
refers to the optional
process output
property of AB UFS to
adjust the duration of
the temporary Fire
=> [T022.S035-
2I058.020] Operation
of ‘Fan Boost’, ‘Fire
Place’ prolong time
settings