Installation Instructions

Model PSR-1
Remote Power Supply

P/N 315-090911-23

Figure  1

PSR-1 Remote Power Supply

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

INTRODUCTION

The Model PSR-1 from Siemens Industry, Inc.,
(See Figure 1) is a microprocessor controlled
remote power supply and battery charger used
with the MXL System. It operates with an
MPS-6 or MPS-12 to provide 6 or 12 amps,
respectively, of power for various MXL mod-
ules.

In addition, the PSR-1 acts as an interface
between remote option modules and the MXL
when used with a NET-4 plug-in communica-
tion module (See Instructions P/N 315-090909)
or NET-7 plug-in communication module (See
Instructions P/N 315-091914).

The PSR-1 can also be used to power an
MOI/MOD annunciator driver set. In addition, the
PSR-1 can be used as an auxiliary power supply
in a standalone mode without an MXL.

The PSR-1 has LED status indicators for:

POWER ON, 5V AUX ON, 24V ON, BAT TRBL,
TB3 TRBL 

(Class A power limited output for the

CZM-1 and PS-5), 

GND FAULT, XMIT, ANY

TRBL, 

and 

ANY ALARM

. The PSR-1 has two

relays used for common alarm and common
trouble. These relays also can be programmed
for local alarm and local trouble using CSG-M.

For additional information on the MXL/MLV
System, refer to the 

MXl/MXLV Manual,

P/N 315-092036.

Summary of Contents for PSR-1

Page 1: ...s an interface between remote option modules and the MXL when used with a NET 4 plug in communica tion module See Instructions P N 315 090909 or NET 7 plug in communication module See Instructions P N 315 091914 The PSR 1 can also be used to power an MOI MOD annunciator driver set In addition the PSR 1 can be used as an auxiliary power supply in a standalone mode without an MXL The PSR 1 has LED s...

Page 2: ...l Standby 24 VDC Module Current 3 Total the right hand column and record it at the bottom of the form opposite Total System Current 4 For NFPA 72 Local and 72 Proprietary systems multiply the total system current by 24 and record it at that Total AH location or For NFPA 72 Municipal Tie and 72 Remote Station systems multiply the total system current by 60 and record it at that Total AH location or...

Page 3: ...O M A m 2 0 0 7 I O M A m 0 2 0 0 4 T E N A m 5 0 0 7 T E N A m 0 3 0 0 M 7 T E N A m 0 3 0 0 W 1 M I N A m 0 6 0 0 W 1 M I N M 1 M I N h t i w A m 0 3 1 0 0 1 C C O A m 5 1 0 0 1 L A P 2 e t o N e e S 0 0 1 M I P A m 5 1 0 0 2 M I P 2 e t o N e e S 0 0 A 5 S P d a o l V 5 f o A m 0 1 0 0 7 N 5 S P d a o l V 5 f o A m 5 4 0 0 2 F 1 1 C C R 1 E S R R 2 f i A m 5 1 A m 5 5 d e s u s i 1 M I P 0 0 C ...

Page 4: ... l e r A m 0 1 4 M S C x a m A 5 1 A m 0 7 t i u c r i c r e p A m 0 1 6 B 1 1 M Z C A m 0 5 0 0 4 M Z C A m 5 6 7 m r a l a n i s e n o z 4 A m 0 1 P C 0 0 3 2 D 0 0 A m 0 0 2 E 1 1 T C D A m 0 9 1 0 0 1 C M D 0 0 A m 0 2 6 B 1 1 P C I d a o l e c i v e d A 0 1 x a m A 5 1 0 0 T C A D M A m 0 6 2 0 0 6 1 D I M x a m A m 8 4 A m 2 4 2 B K M 0 0 A m 5 7 C 5 B K M A m 0 0 3 0 0 C 6 6 B K M A m 0 0 3...

Page 5: ...r BATTERY VOLTAGE THRESHOLDS Battery Status Conditions Battery Voltage Volts Battery Not Installed 14 0 Charger Disabled 18 3 Battery Low Fault On Battery 21 0 Battery Low Fault On AC 24 0 Battery High Fault 30 0 Security Mode UL 1076 Operation S2 5 To Disable the Tamper Switch The PSR 1 does not support the use of security points from initiating circuits in its enclosure To disable the tamper swi...

Page 6: ... X O O X X O X X X O X X X O X X X O O O O X X X X O X O O X X X X O O X O X X X X O X X O X X X X O O O X X X X X O X O X X X X X O O X X X X X X O X X X X X X X O 8 2 1 9 2 1 0 3 1 1 3 1 2 3 1 3 3 1 4 3 1 5 3 1 6 3 1 7 3 1 8 3 1 9 3 1 0 4 1 1 4 1 2 4 1 3 4 1 4 4 1 5 4 1 6 4 1 7 4 1 8 4 1 9 4 1 0 5 1 1 5 1 2 5 1 3 5 1 4 5 1 5 5 1 6 5 1 7 5 1 8 5 1 9 5 1 0 6 1 1 6 1 2 6 1 3 6 1 4 6 1 5 6 1 6 6 1 7...

Page 7: ...HE NETWORK CONNECTION TB4 For the PSR 1 to communicate with the MXL a NET 4 or NET 7 network interface card must be installed into P7 of the PSR 1 For a NET 4 con Figure 3 Mounting the PSR 1 on the MBR MP nect the MXL network MMB to terminals 1 and 2 of TB4 as indicated in Figure 4 Terminate the shield at the MMB only For a NET 7 refer to Figure 2 of the NET 7 Installation Instructions P N 315 091...

Page 8: ...f 4 ohms max T tapping is not allowed b Refer to Figure 8 Class B wiring can be used to obtain the maximum of 40 CZM 1s Each Class B wire run can support a maximum of Figure 6 Common Alarm and Common Trouble Relays Figure 7 CZM 1 Power Class A Wiring 6 5 4 3 2 1 TB1 COMMON TROUBLE RATINGS 2A 30 VDC RESISTIVE COMMON ALARM REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 ...

Page 9: ...ual Class B power runs for a total of 40 devices for example 12 8 6 and 14 CZM 1s with each of the four runs not exceeding 4 ohms resistance T tapping is allowed provided the total resis tance of all wires does not exceed 4 ohms 6 Refer to Figures 9 and 10 for wiring instruc tions for the PS 5A MOI 7 Power P9 The PSR 1 may be used in standalone mode as the power supply for the MOI 7 In this config...

Page 10: ...is provided on TB3 for the MOM 4 card cage This output is rated at 6 amps MPS 6 or 12 amps MPS 12 18 31 VDC This capacity must be derated by the current drawn by the CZM 1 and PS 5A power output If the full 2 amp capacity of the CZM 1 and PS 5A output is used the MOM 4 power must be derated to 4 amps MPS 6 or 10 amps MPS 12 See Figure 13 for wiring instruc tions When a PSR 1 is used with an MKB 2 ...

Page 11: ...onnect as shown in Figure 16 Figure 14 Connecting a NET 7 in a MOM 4 REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 REVISION 6 OR HIGHER FOR ADDITIONAL WIRING INFORMATION REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 REVISION 6 OR HIGHER FOR ADDITIONAL WIRING INFORMATION REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 3...

Page 12: ...ting OMM 1s and MOM 4s with a PSR 1 REFER TO WIRING SPECIFICATION FOR MXL MXL IQ AND MXLV SYSTEMS P N 315 092772 REVISION 6 OR HIGHER FOR ADDITIONAL WIRING INFORMA TION POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT 30K OHMS FOR TB3 1 6 ...

Reviews: