PXC3.E...    Room automation stations 

CM1N9203en_05 

Building Technologies 

 

2015-11-23 

Island bus interface 

 

 

   Communications 

Interface type 

Siemens specific protocol 

   DC output 

Nominal voltage 

DC 24V 

 

Max. current  

600 mA  

(sufficient for typically 8 TX-I/O modules) 

 

Parallel switchable with 3 supply 

modules TXS1.12F10  

For details, see: TX-I/O planning and 

installation manual, CM110562)  

 

Short-circuit proof, overload-proof 

Self-resetting 

 

Protection 

Short-circuit proof 

Island bus connector on 

side 

Protection against faulty wiring with 

AC 24 V 

No electric protection. 

Use the terminal cover. 

 

 

 

KNX PL-Link interface 

 

 

    Communications 

Interface type 

KNX, galvanically separated 

 

Transceiver 

TP-UART 

 

Baud rate 

9.6 kbps 

    Bus power supply 

Nominal voltage 

DC 29 V 

 

Max. supply  

 

Note: for devices with higher power 

requirement, use the output AC 24 V 

2 A, see above.

 

160 mA for max 32 devices with KNX 

PL-Link. Default: Auto detection; must 

be turned off via ABT if external bus 

supply is used. 

Up to 64 devices with KNX PL-Link can 

be operated using one or two external 

bus supplies. 

 

Protection  

Short-circuit proof  

Protection against miswiring up to AC 24 V 

 

 

 

DALI interface 

 

 

    Communications 

Interface type 

DALI, galvanically separated  

 

Baud rate 

1.2 kBit/s 

 

Insulation strength 

Reinforced insulation for 230 V (1.5 kV) 

Suitable for installations in overvoltage 

category III (4 kV). 

    Bus power supply 

Nominal voltage 

DC 16 V 

 

Max. current  

128 mA for max 64 DALI devices 

 

Protection  

Short-circuit proof  

Upon power-on, AC 230 V bus voltage is 

recognized on terminals DA+ and DA–. 

 

NO protection against miswiring with AC 24 V or AC 230 V: 

Voltage between DA+ / DA+ or between DA– / DA– will destroy the DALI PCB! 

 

 

 

Wiring, topology, cable 

length, cross section 

See installation manual TRA, CM111043. 

 

 

 

 

Connection terminals,  

plug-in 

Construction type 

Copper-wire or Cu-strand  

   with wire end sleeve 

Copper-strand without  

   wire end sleeve 

Pluggable screw terminals 

1 x 0.6 mm dia. to 2.5 mm

2

 (22 to 14 AWG) 

or 2 x 0.6 mm dia. to 1,0 mm

2

          

(22 to 18 AWG) 

1 x 0.6 mm dia. to 2.5 mm

2

 (22 to 14 AWG) 

or 2 x 0.6 mm

 to 1.5 mm

2

     (22 to 16 AWG) 

 

Screwdriver 

Slot screws  

Screwdriver, size 1 

 

Max. tightening torque 

0.6 Nm (0.44 lb-ft) 

 

 

 

 

 

 

 

Summary of Contents for PXC3.E16A100A

Page 1: ...island bus to connect TX I O modules with any data point mix including bus supply Optional KNX PL Link peripheral bus to connect sensors actors and room units including bus supply Optional DALI bus to connect ballasts including bus supply Optional Connection of individual devices with KNX S Mode via KNX PL Link Ethernet switch for communication and tool connection USB Device interface Operating vo...

Page 2: ...gments 1 140 3 max 64 devices max 72 physical I O points max 64 ballasts 4 PXC3 E75 100A S55376 C132 typically 8 rooms typically 16 room segments 1 280 3 max 64 devices max 200 physical I O points PXC3 E75A 100A S55376 C133 typically 8 rooms typically 16 room segments 1 280 3 max 64 devices max 200 physical I O points max 64 ballasts 4 V5 1 V5 1SP 2 PXC3 E72 S55376 C100 typically 4 rooms typically...

Page 3: ...rcially available devices with KNX S Mode requires ETS engineering The DALI bus supports lighting control Commercially available DALI EBGs electronic ballasts can be connected Equipment combinations Depending on the type PXC3 series room automation stations can be operated with TX I O devices and devices with KNX PL Link DALI device type Description Supported 0 Fluorescent Lamps Yes 7 Switching Fu...

Page 4: ... bus supplies for island bus KNX PL Link and DALI are integrated in the room automation station For better reliability of the room automation station the bus supplies and the AC 24 V outlets are independent from the room automations station s own supply V6 The bus supplies are switched on by default and can be swiched off via tool if not needed V5 1 The bus supplies are switched off automatically ...

Page 5: ...X PL Link communication KNX PL Link not used or communication fault DALI Yellow Continuously ON Flashing Continuously OFF OK DALI bus communication DALI not used or communication fault SVC Red Continuously OFF Blinking Blinking per wink command OK No application loaded Physical identification of the room automation station Ether net 1 2 Green Continuously ON Continuously OFF Flashing Link active L...

Page 6: ...ed onto the mounting rail on the right side of the room automation station The island bus is created automatically in this process Recommended With restrictions Wall horizontal from left to right or from right to left Over head On a horizontal surface Wall vertical from bottom to top or from top to bottom Ambient temperature 5 50 C 23 122 F Ambient temperature 5 45 C 23 122 F 50 C 122 F is admissi...

Page 7: ...not used The NX PL Link supply MUST be switched off via tool if an external bus supply is used Transit power AC 24 V TX IO island bus KNX PL Link AC 24V terminals 3 4 AC 24 V 6 A terminals 7 and 8 for additional AC 24 V consumers 144 VA 6 A 48 VA 2 A 144 VA 6 A only if the sum of 10 A at terminals 5 and 6 is not exceeded Fusing of the supply outputs for field supply AC 24 V 2 A KNX PL Link termina...

Page 8: ... to 64 devices with KNX PL Link can be operated using one or two external bus supplies Protection Short circuit proof Protection against miswiring up to AC 24 V DALI interface Communications Interface type DALI galvanically separated Baud rate 1 2 kBit s Insulation strength Reinforced insulation for 230 V 1 5 kV Suitable for installations in overvoltage category III 4 kV Bus power supply Nominal v...

Page 9: ... residential commercial and industrial environments RCM conformity EMC See CM1T9222en_C1 UL approbation UL 916 EAC Eurasian conformity For all PXC3 E 100A types Meets the requirements for eu bac certification excepted PXC3 E16A 100A See product list on http www eubaccert org licences by criteria asp License Application Control accuracy K 212196 Fan Coil 4 pipe Heating Cooling 0 3 0 1 Environmental...

Page 10: ...t circuit proof with PTC resistor X X 8 24 V Operating voltage AC 24 V X X X 8 24 V 6 A Output AC 24 V to supply other PXC3 room automation stations internally connected to 24 V on pcb no internal fusing X X X F T 10 A fuse for island bus conductor V X X USB USB interface X X X 12 DALI DALI bus connection X X Service Service pin Ethernet X X X DALI DALI test X X Without labels Island bus The islan...

Page 11: ...en_05 Building Technologies 2015 11 23 24V CS 5 6 7 8 V 9203z05_01 T 10A 9 10 11 12 24V 24V 2A KNX 2 PTC KNX Island bus DALI DALI 3 1 2 3 4 Island Bus 1 1 2 Not with PXC3 E16A 100A 3 Only with PXC3 E A types Basic circuit diagram connections AC 24 V fusing ...

Page 12: ...12 12 Siemens PXC3 E Room automation stations CM1N9203en_05 Building Technologies 2015 11 23 Dimensions 9203M01 All dimensions in mm 2012 Siemens Switzerland Ltd Subject to change ...

Reviews: