4 / 10
Siemens
PXG3... BACnet router for Ethernet - LONWORKS - MS/TP
CM1N9270en_06
Building Technologies
2014-06-11
LEDs
RUN
FLT
HMI/Tool
LED
Color
Activity
Function
RUN
Green
·
Continuously ON
·
Continuously OFF
·
Flashing
·
Device ready.
·
At least one internal power supply out
of range.
·
Start-up of device.
FLT
Red
·
Continuously OFF
·
Continuously ON
·
Flashing
·
OK
·
HW fault or program fault.
·
Incorrect or corrupt FW.
INF
--
--
(Not used)
COM1
Yellow
·
Flashing
·
Sends MS/TP packages.
COM2
Yellow
·
Flashing
·
Sends L
ON
W
ORKS
packages
(PXG3.L only).
SVC Red
·
Continuously OFF
·
Continuously ON
·
Flashing
·
Flashing per wink
command *)
·
Configured.
·
Defective Hardware.
·
Unconfigured.
·
Physical identification of the router.
9
27
0
Z
05
8 7 6 5 4 3 2 1
Ethernet
1 / 2
Green
·
Continuously ON
·
Continuously OFF
·
Flashing
·
Link active
·
Link inactive
·
Network activity
Yellow
·
Continuously ON
·
Continuously OFF
·
Link 100 Mbps
·
Link 10 Mbps
*)
Wink command
pattern:
2s
1s
21s
5 Hz
5 Hz
9222z02
2s
1s
1
9
27
0
z0
3
Button Press
Description
1
·
Short
Physical identification on the network (Ethernet).
To reset the device into the factory state please follow these steps:
1. Power off device.
2. Power on the device.
3. Wait for all LEDs to light up and turn off again,
then push down SVC button.
4. Keep SVC button pressed until the green RUN LED flashes,
then release button.
5. Wait for device to fully start up unconfigured
(RUN LED on, SVC LED flashes).
The device has now lost any password and other settings.
Only the IP network settings remain the same as before.
Service button