Basic Documentation QAA73.110 Room unit
CE1P2284en
HVAC Products
Description
of enduser settings
10.07.2002
3.15 Summer / winter changeover temperature
The summer / winter changeover temperature is the criterion for automatic summer /
winter changeover of the heating plant.
It offers the following benefits:
•
Fully automatic operation throughout the year
•
The heating will not be switched on when the outside temperature drops for short
periods of time
•
Additional savings function
1. Press the line selection buttons to select line 46.
2. Press the + / – buttons to select the summer / winter changeover temperature.
Setting range
Unit
Factory setting
8 ... 30.0
°C
17
By changing the setting, the respective periods of time will be shortened or extended.
The change will only affect the heating circuit.
Entry:
Increase:
Winter operation will start
earlier
Summer operation will start
later
.
Decrease:
Winter operation will start
later
Summer operation will start
earlier
To determine changeover, the setting of the summer / winter changeover temperature
( ± a fixed switching differential) is compared with the attenuated outside temperature.
Heating
OFF
(from winter to summer)
TAged > SuWi +1 °C
Heating
ON
(from summer to winter)
TAged < SuWi -1 °C
•
This function only acts in automatic mode
•
During summer operation, Info line 4 Eco is displayed
ON
17
T
SuWi
TAged
°C
H
OFF
t
22
84
D
04
en
SuWi +1 °C
SuWi -1 °C
16
18
19
20
5
0
10
15
Changeover between summer and winter operation:
TAged
Attenuated outside temperature
SuWi
Summer / winter changeover temperature
T
Temperature
t
Time in days
H
Heating
Description
Line 46
Effect
Changeover
Notes