40/70
Siemens Building Technologies
Basic Documentation QAA73.110 Room unit
CE1P2284en
HVAC Products
Description
of the heating engineer settings
10.07.2002
4.13 Minimum and maximum limitation of flow
temperature HC1 and HC2
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary. They prevent too low or too high flow temperatures.
1. Press the line selection buttons to select line
71, 72, 81
or
82
.
2. Press the + / – buttons to set the required limitations of the flow temperature.
Line
Setting range
Unit
Factory setting
71
8...TV1max
°C
8
72
TV1min...TKmax
°C
80
81
8...TV2max
°C
8
82
TV2min...TKmax
°C
80
...TKmax
Maximum boiler temperature
TV1max
Maximum limitation of flow temperature HC1
TV1min ... Minimum limitation of flow temperature HC1
TV2max
Maximum limitation of flow temperature HC2
TV2min
Minimum limitation of flow temperature HC2
0
10
20
30
40
50
60
70
80
90
100
TV
max
min
akt
°C
228
4Z21
TVw
71/81
72/82
TVw Current flow temperature setpoint
71
minimum limitation of flow temperature
72
maximum limitation of flow temperature
81
minimum limitation of flow temperature
82
maximum limitation of flow temperature
These settings provide maximum or minimum limitation of the flow temperature.
Maximum limitation is
not
to be regarded as a safety function as required with
underfloor heating systems, for example.
Description
Lines
71 and 72 for HC1
81 and 82 for HC2
Effect
Important