background image

4/6 

Siemens 

QAX30.1, QAX31.1 – Room units with PPS2 interface 

CA2N1741en_02 

Building Technologies 

 

2015-12-23 

Technical data  

 

Supply voltage 

Operating voltage range 

DC 12...15 V (SELV) 
DC 12…15 V class 2 (US) 

 

The room unit receives its power from the connected controller, via the PPS2 interface 

 

Power consumption (from controller) 

Max. 0.10 VA 

Function data 

Temperature sensor 

 

 

Measuring element 

NTC resistor 

 

Measuring range 

0 ... 40 °C 

 

Response time 

 8 min 

 

Accuracy (5 ... 30 °C) 

±

 0.5 K 

 

Accuracy (25 °C) 

±

 0.25 K 

 

Setpoint correction 

 

 

Correction range (determined by controller) 

max. 

±

 12 K (default 

±

 3 K) 

 

Accuracy over full correction range 

10 % 

Interfaces 

Type of interface between controller and room unit   PPS2 (point-to-point interface,  

Version 2) 

 

Baud rate 

4.8 kbit/s 

Cable connections 

Connection terminals (screw terminals) 

Stranded or solid conductors   
0.8 ... 2.5 mm

2

 

 

Single cable length controller – Room unit 

See Installation guidelines: 
Desigo RXC: CA110334,  
Desigo RXB & RXL: CM110381 
Desigo RXA: CA2Z3884 
Desigo PX:    CA110396 

 

 

2-core or 4-core, twisted pairs,  
unscreened  

 

Connecting cable for service tool 

Off-the-shelf, max. 3 m 

Protection data  

Housing protection  

IP 30 to EN 60529 

 

Protection class 

III to EN 60730-1 

Ambient conditions 

IEC 721 

Operation 

Transport 

 

Ambient air conditions 

Class 3K5 

Class 2K3 

 

Temperature 

0 ... 50 °C 

– 25 ... 70 °C 

 

Humidity 

< 85 %rH 

< 95 %rH 

 

Mechanical conditions 

Class 3M2 

Class 2M2 

Standards, directives 
and approvals 

Product standard  

EN 60730-1 

Automatic electrical controls for house-
hold and similar use 

 

Electromagnetic compatibility (Applications) 

For use in residential, commerce, light-
industrial and industrial environments 

 

EU conformity (CE) 

CA2T1741xx   *) 

 

UL certification (US) 

UL916,   

http://ul.com/database

 

 

RCM-conformity (EMC) 

A5W00005055   *) 

 

EAC conformity 

Eurasia conformity 

Environmental  
compatibility 

Product environmental declaration (contains data on 
RoHS compliance, materials composition, packaging, 
environmental benefit, disposal) 

A6V10736277_en--_a  *) 

Dimensions 

See “Dimensions” 

 

Color 

Housing front, dial 

NCS S 0502-G, 

 RAL 9003 signal white 

 

Housing, base unit 

RAL 7035 light grey 

Weight 

Excluding packaging 

0.12 kg 

 
*) The documents can be downloaded from 

http://siemens.com/bt/download

. 

 
 

Summary of Contents for QAX30.1

Page 1: ...ket for commissioning and service tool or service terminal Use The room units are used in rooms controlled by an individual room control system to measure the room temperature and in the case of the QAX31 1 to adjust the room temperature setpoint They can also be used in conjunction with a Desigo PXC automation station The room units incorporate a socket for a commissioning and service tool or ser...

Page 2: ...or mounting on a recessed conduit box with the cables connected from the rear The unit comprises a housing and base unit connected by releasable snap fittings The base unit accommodates the screw terminals which have an integrated terminal strip The housing accommodates a printed circuit board room temperature sensor element setpoint adjuster plug in connectors and a socket for the commissioning a...

Page 3: ... cables Desigo PX uses two core cables see the respective installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recessed conduit box Do not mount in recesses shelves behind curtains or doors or above or near heat sources Avoid exposure to direct sunlight or draughts The electrical wiring conduit must be sealed where it joins the ro...

Page 4: ...PX CA110396 2 core or 4 core twisted pairs unscreened Connecting cable for service tool Off the shelf max 3 m Protection data Housing protection IP 30 to EN 60529 Protection class III to EN 60730 1 Ambient conditions IEC 721 Operation Transport Ambient air conditions Class 3K5 Class 2K3 Temperature 0 50 C 25 70 C Humidity 85 rH 95 rH Mechanical conditions Class 3M2 Class 2M2 Standards directives a...

Page 5: ... Device supply Data PPS2 pos CP 2 Device supply Data PPS2 neg Bus connection looped to tool socket C 3 With LONWORKS bus Desigo RXC CLA C 4 With LONWORKS bus Desigo RXC CLB 5 8 Not used Standard type RJ45 tool socket 1 3206Z01 2 3 45 67 8 With LONWORKS bus Desigo RXC CLA With LONWORKS bus Desigo RXC CLB Not used Not used Not used Not used CP Data PPS2 CP Data PPS2 Connection diagram Example RXC Th...

Page 6: ...5 32 36 4 2 60 80089 90 100 56 60 56 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2000 Delivery and technical specifications subject to change ...

Reviews: