QAX34.1 – Room unit with PPS2 interface 

CA2N1645en_02 

Building Technologies 

 

30 Jun 2009 

Connection terminals 

The tool socket on the room unit provides access to the connected individual room 
controller via the commissioning and service tool or the service terminal.  

The bus cable (Terminals 3 and 4) is therefore looped to the tool socket (Pins 1 and 2).  
The bus cable is not affected by the room unit.  

For connection of a service terminal, the PPS2 interface (Terminals 1 and 2) is also 
connected to the tool socket. 
 

8

7

6

5

4

3

2

1

C–

C+

CP

CP

+

80085

 

PPS2 interface, supply voltage 

CP+ 

Device supply, Data PPS2 (pos.) 

CP– 

Device supply, Data PPS2 (neg.)

 

Bus connection (looped to tool socket) 

C+ 3  With 

L

ON

W

ORKS

® bus (DESIGO RXC): CLA 

C– 4  With 

L

ON

W

ORKS

® bus (DESIGO RXC): CLB 

 

5 ... 8 

Not used

 

 
Standard type RJ45 tool socket. 
 

1

320

6Z01

2 3 4 5 6 7 8

 

With L

ON

W

ORKS

® bus (DESIGO RXC): CLA 

With L

ON

W

ORKS

® bus (DESIGO RXC): CLB 

Not used 
Not used 
Not used 
Not used 
CP+  

Data PPS2 

CP– Data 

PPS2 

 

Connection diagram (Example: RXC) 

The following example shows the room unit connected to a DESIGO RXC room  
controller: 
 

17

41

A

03

PPS2

Tool

A

R1

B

7 8 1 2

4 3 2 1

C–

C+

CP

CP

+

N1

CP

+

CP

CLA

CLB

PPS2

LonWorks® Bus

  

 = Twisted pair 

 
R1 Room 

unit 

QAX34.1 

N1 Room 

controller 

RXC... 

Connection for RXT10 commissioning and service tool 

Connection for service terminal with PPS2 interface 

 
 
 
 

Terminal layout 

Tool socket  

.
.
.

Summary of Contents for QAX34.1

Page 1: ...it is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of the room controller The functions of the LCD display are determined by the controller If manual fan speed control is enabled the room unit is suitable for control of a fan coil system It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorp...

Page 2: ...etpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80083 80084 Socket for the commissioning and service tool or service terminal 80166A Room temperature display and sequence heating or cooling Rocker switch for room temper...

Page 3: ...ress the switch once to switch from a display of the current room temperature to a display of the setpoint Each further operation of the or switch raises or lowers the setpoint by 0 5 K or 1 0 F the unit of measurement is determined by the controller The controller also determines the maximum adjustment range allowed In normal operation the following may be displayed depending on the controller co...

Page 4: ...oom units may be connected to a PXC automation station they are identified by different settings of their address plugs A twisted pair cable is required for the connection to the controller DESIGO RX uses four core cables DESIGO PX uses two core cables see the respec tive installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recess...

Page 5: ...ce tool initiates a wink command the type of controller connected will be displayed on the room unit For example Controller type Display RXC21 1 RXC30 1 Operating notes During operation and commissioning the LCD display also indicates errors as follows Display Description Error type C No communication with controller for more than 64 s 02 Firmware version e g Version 2 0 D Room temperature sensor ...

Page 6: ...IGO RXC CA110334 DESIGO RXB RXL CM110381 DESIGO RXA CA2Z3884 DESIGO PX CA110396 Cable type 2 core or 4 core twisted pairs unscreened Connecting cable for service tool Off the shelf max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions IEC 721 Operation Transport Ambient air conditions Class 3K5 Class 2K3 Temper...

Page 7: ...voltage CP 1 Device supply Data PPS2 pos CP 2 Device supply Data PPS2 neg Bus connection looped to tool socket C 3 With LONWORKS bus DESIGO RXC CLA C 4 With LONWORKS bus DESIGO RXC CLB 5 8 Not used Standard type RJ45 tool socket 1 3206Z01 2 3 45 67 8 With LONWORKS bus DESIGO RXC CLA With LONWORKS bus DESIGO RXC CLB Not used Not used Not used Not used CP Data PPS2 CP Data PPS2 Connection diagram Ex...

Page 8: ...ns QAX34 1 Room unit with PPS2 interface CA2N1645en_02 Building Technologies 30 Jun 2009 Dimensions 9 5 32 34 4 2 60 80088 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Reviews: