QFA1000 

 

 

 

 

 

Room Hygrostats 

QFA1… 

 

for relative humidity 

 

 

 

 

 

Hygrostat with single-pole microswitch 

 

Humidity measuring element made of stabilized plastic texture 

 

Setpoint knob for the upper switching point 

 

For controlling humidification equipment 

 

For controlling dehumidification equipment 

 

For mounting directly on the wall or on a recessed conduit box 

Use 

The room hygrostats are used for controlling and monitoring relative humidity in ventila-
tion or air conditioning plant. 
They ensure room humidity control within the selectable range of 30 to 90 % relative 
humidity by controlling humidification or dehumidification equipment. 

They can also be used for monitoring minimum or maximum humidity levels. 

Type summary 

Type  
reference 

Setpoint setting 

range 

Switching differential 

1)

 

Setpoint  

knob 

Statically 

Dynamically 

QFA1000 

30…90 % r. h. 

Approx. 4 % r.h. 

6 % r.h. 

Internally 

QFA1001 

30…90 % r. h. 

Approx. 4 % r.h. 

6 % r.h. 

Externally 

1) 

The static switching differential is determined at a constant ambient humidity by turning the setting 
knob. 
The dynamic switching differential is determined by changing the ambient humidity while maintain-
ing the same setpoint adjustment; only the dynamic switching differential is of practical value. 

CE1N1518en 
2014-07-30 

 

Building Technologies

 

 

Summary of Contents for QFA1 Series

Page 1: ...ectable range of 30 to 90 relative humidity by controlling humidification or dehumidification equipment They can also be used for monitoring minimum or maximum humidity levels Type summary Type reference Setpoint setting range Switching differential 1 Setpoint knob Statically Dynamically QFA1000 30 90 r h Approx 4 r h 6 r h Internally QFA1001 30 90 r h Approx 4 r h 6 r h Externally 1 The static sw...

Page 2: ...s reason recalibration may be required in due time At temperatures other than the calibration temperature the switching point drifts sys tematically temperature influence Also in the case of fast humidity changes the switching point will temporarily be shifted Mechanical design The room hygrostat is designed for wall mounting It fits on most commercially available recessed conduit boxes The cables...

Page 3: ... The devices are considered electronics devices for disposal in term of European Directive 2012 19 EU and may not be disposed of as domestic waste Dispose of the device via the channels provided for this purpose Comply with all local and currently applicable laws and regulations Technical data Setpoint setting range 30 90 Humidity measuring element stabilized plastic texture band Control mode 2 po...

Page 4: ... downloaded from http siemens com bt download Connection diagrams 1 2 3 1518G01 ϕ 1 2 Humidification 1 3 Dehumidification Diagram 1 Humidification Diagram 2 Dehumidification 1 2 3 1518A01 ϕ T5A L N AC 230 V ϕ 1 2 3 1518A02 ϕ T5A L N AC 230 V ϕ Dimensions 1518M01 60 70 80 90 50 30 76 76 34 60 7 5 4 2 4 Dimensions in mm Environmental conditions Materials and colors Directives and Standards Weight In...

Reviews: