background image

CC1N7714en 
17.07.2006 

Building Technologies

HVAC Products

 

 

7

714

 

 

QRB1...A with large flange 

QRB1...A with small flange 

QRB1...B 

QRB3... with 

 

and clamp 

and clamp 

with plug 

flange and clamp 

 

 

 

 

Photoresistive  
Flame Detectors 

QRB1...
QRB3...

 

 

Photoresistive detectors for use with Siemens burner controls, for the supervi-
sion of oil flames in the visible light spectrum. 
The QRB… are used primarily in connection with oil burner controls in intermit-
tent operation. 
 
The QRB... and this Data Sheet are intended for use by OEMs which integrate the 
flame detectors in their products. 

Use 

The QRB... flame detectors are designed for the supervision of yellow-burning oil 
flames in connection with burner controls type LAL..., LOA..., LMO... and LMV… 
They are suited for frontal or lateral (90°) illumination. 
 
The maximum spectral sensitivity of the QRB… is about 600 nm, thus giving full con-
sideration to the maximum level of visible light radiation of yellow-burning oil flames. 
Since the QRB… also acquires certain parts of the radiation spectrum of other light 
sources (boiler room lighting, solar radiation, etc.), the standard regulations regarding 
safety in connection with extraneous light still apply. 

Summary of Contents for QRB1 Series

Page 1: ...ntended for use by OEMs which integrate the flame detectors in their products Use The QRB flame detectors are designed for the supervision of yellow burning oil flames in connection with burner controls type LAL LOA LMO and LMV They are suited for frontal or lateral 90 illumination The maximum spectral sensitivity of the QRB is about 600 nm thus giving full con sideration to the maximum level of v...

Page 2: ...otes Ensure that the relevant national safety regulations are complied with Installation notes Always run the detector cable separate from other cables especially from the high voltage ignition cable while observing the greatest possible distance It is important to achieve practically disturbance and loss free signal transmission Never run the detector cable together with other cables Line capacit...

Page 3: ... always correctly sited towards the flame Flame detector with soft plastic plug For mounting this type of detector on the burner all that is required is a hole with a lateral groove refer to Dimensions The sealing and securing ribs of the soft plastic plug hold the detector firmly in the hole The guide spring guarantees correct alignment of the photoresistive element with the flame Small flange 21...

Page 4: ...B70A x 50 70 70 Without Ferrule QRB1A A070B70A1 x 50 70 70 Without Ferrule x QRB1A A070B70A2 x 50 70 70 Without Ferrule x QRB1A A070B70B x 50 70 70 With Ferrule QRB1A A080B70A x 50 80 70 Without Ferrule QRB1A A148B70B x 50 148 70 With Ferrule QRB1A A150B70A x 50 150 70 Without Ferrule QRB1A A150B70A1 x 50 150 70 Without Ferrule x QRB1A A150B70A2 x 50 150 70 Without Ferrule x QRB1A B027A25A x 65 27...

Page 5: ...A25A x 65 30 25 Without Unstripped QRB1B B035B40A x 65 35 40 Without Ferrule QRB1B C036B40A x 105 36 40 Without Ferrule QRB1B D025B40B x 137 25 40 With Ferrule QRB1B D042B20B x 137 42 20 With Ferrule QRB1C A050B40A x 50 50 40 Without Ferrule QRB1C B030A25A x 65 30 25 Without Unstripped QRB1C B080B70A x 65 80 70 Without Ferrule Item Part number Small flange 21 mm spacing 4 241 1462 0 Large flange 3...

Page 6: ...N 60721 3 1 Climatic conditions class 1K3 Mechanical conditions class 1M2 Temperature range 20 60 C Humidity 95 r h Transport DIN EN 60 721 3 2 Climatic conditions class 2K2 Temperature range 20 60 C Humidity 95 r h Operation DIN EN 60 721 3 3 Climatic conditions class 3K5 Mechanical conditions class 2M2 Temperature range 20 60 C Humidity 95 r h Condensation formation of ice and ingress of water a...

Page 7: ...6 0 26 4 6 45 36 16 4 241 1600 0 13 5 8 8 9 g l m 4 6 26 45 36 9 4 286 1490 0 79 4 186 8806 0 10 QRB3 20 7 A A 7714m04e 0706 14 2 15 6 2 17 QRB1 A without plug QRB1 B with plug QRB3 A m l 8 8 g A QRB1 with connector AGK56 38 m l 8 8 g A QRB1 with connector AGK53 0 2006 Siemens Building Technologies HVAC Products GmbH Subject to change ...