background image

2

Installation:

•  Open the door by unscrewing the door knob.
•  Mount the starter enclosure vertically on a rigid surface 

free from vibration. Refer Fig. 5. 

•  Remove the rubber Grommets for incoming and outgoing 

cable connections. (Fig. 2).

•  Connect incoming and outgoing cables as follows:  

(Fig. 2)

  –  Select correct size of cable from Table 1.
  –  Remove approx. length of insulation as per following 

table:

Length of insulation 

removal (mm)

Cu cable size 

(mm

2

)

10

10

6

4 and 2.5

5

1.5

  –  Pass the cable through proper cable gland to avoid 

ingress of material.

  –  Connect the incoming supply cables to terminal 

block TB1 (Fig. 2) and tighten the screws firmly (ref. 
tightening torque from Table 2).

 

NOTE:

 LMRA is set in Manual mode (Factory setting)

•  Set the overload relay scale (Fig. 2) using proper 

screwdriver as follows:

  –  Set the overload relay to rated current mentioned on 

motor name plate.

  –  Press green button of the contact block CB1 (Fig. 2) 

to start the motor and wait till it reaches to normal 
speed. Reduce the overload relay settings till it trips.

  –  Set the overload relay at slightly higher value.
  –  Allow a reset time appr. 4 min. and reset the overload 

relay manually.

  –  Restart the motor. If the relay does not trip, consider 

the overload relay as properly set. 

    If it trips, set it at little higher value and recheck.
  –  Press the red knob (Fig. 2) on the overload relay to 

stop the motor.

  –  Fix the door by screwing the knob.

Replacement of coil

Fig. 3: Contactor – Relay connection

Operation:

•  Ensure the door is closed.
  –  Rotate the Latch away from OFF push button.
  –  Check the status of amber LED. Ensure that amber LED 

is continuously ON and then only proceed.

  –  Switch ‘ON’ the starter by pressing the green push 

button (marked ‘I’) (Fig. 1) on starter door.

  –  To Switch ‘OFF’ the starter press red push button 

(marked 

‘O’

) (Fig. 1) on the starter door.

•  Reset Operation
  –  If the overload relay trips, Reset manually.  

(Allow a reset time of approx. 4 min.)

Maintenance:

•  Switch off the starter and put Latch on the OFF push 

button, (marked ‘

O

’). 

Disconnect the main supply by 

switching OFF main switch before maintenance.

•  Keep the interior dust free.
•  Re-tighten the terminal screws from time to time.
•  No maintenance is needed for overload relay. 
  Please do not open the overload relay.
•  Replace the contactors / contacts of the contactors if they 

were severely pitted or when only 40% of the original 
contact tip remains.

  (Contacts replacement possible only for 3TS33, 3TS34, 

3TS35, 3TS36 contactors).

•  Replacement of overload Relay
  I.  Disconnect the cable between Relay terminals T1, T2, 

T3 and Outgoing Terminal Block TB2.

  II.  Loosen the outgoing terminals screws of contactor 

(Fig. 3).

  III.  Disengage the relay terminals & hook from contactor.
  IV.  Take the overload relay of same range.
  V.  Connect & tighten the relay terminals (L1, L2, L3 to 

the contactor terminals (T1, T2, T3).

  VI.  Ensure that the relay hook (Fig. 3) is engaged in the 

slot of the contactor and slide the relay inwards till 
the cover is flush with contactor ribs.

  VII. Reconnect the disconnected Terminal block (TB2) 

wires to relay and check the correctness of the starter 
wiring by referring to the wiring diagram.

Hook on relay for 
engagement

Contactor 
outgoing terminals

Summary of Contents for RAJA+ 3TE7111-2SC18-1A Series

Page 1: ...ng Dial 6 Relay Red Test button 7 Contactor Incoming Terminal Screws 8 Contactor Outgoing Terminal Screws 9 Wiring diagram Label 10 Links 11 Gasket 12 Grommet 13 Enclosure mounting holes 4x 14 Terminal Block TB1 15 Terminal Block TB2 16 Amber LED 17 LMRA 18 LMRA mode selector switch 19 Earthing for customer Fig 1 ADOL Starter Fig 2 ADOL Starter inside view Please read and understand these instruct...

Page 2: ...is closed Rotate the Latch away from OFF push button Check the status of amber LED Ensure that amber LED is continuously ON and then only proceed Switch ON the starter by pressing the green push button marked I Fig 1 on starter door To Switch OFF the starter press red push button marked O Fig 1 on the starter door Reset Operation If the overload relay trips Reset manually Allow a reset time of app...

Page 3: ...ay 3UW5102 2A Thermal Overload Relay 3UW5102 2B Thermal Overload Relay 3UW5202 2C Thermal Overload Relay 3US5600 2D8K Thermal Overload Relay 3US5600 2Q8K Thermal Overload Relay 3US5600 2R8K Coil for 200 400V 3TY7403 0AZ6 Coil for 260 460V Z8 For 3TS32 33 34 contactor 3TY7403 0AW415 Coil for 260 460V Z8 For 3TS35 36 contactor 3TY7443 0AW415 1NO Contact Block 3SB5420 0B 1NC Contact Block 3SB5420 0C ...

Page 4: ...ough authorized dealer PLASTICS Segregate as per material type for recycling through authorized dealer Because of the long lifetime of Siemens Products the disposal guidelines may be replaced by other national regulations when taking the product out of service The local customer care service is available at any time to answer disposal related questions Customer Care Toll free no 1800 220 987 Email...

Reviews: