background image

3

Table 1:

Motor Rating At 415V 

3ph 50Hz 

HP/kW

Starter MLFB 

Contactor MLFB 

Thermal 

Overload relay 

MLFB

Relay 

range 

(A)

 HRC Fuse 

rating 

(A)

*

 Cu 

cable 

size 

(mm

2

)

Max. Full Load Current 

(A) 

Motor

Submersible 

Pump

Motor

Submersible 

Pump

7.5 / 5.5

7.5 / 5.5

3TE7111-2SC18-1Axx

3TS3210-0Axx-08K

3UW5102-2A

10–16

 32A

2.5

11.4

14.5

10 / 7.5

3TE7111-2BC21-1Axx

3TS3311-0Axx-08K

3UW5102-2B

12.5–20

 32A

2.5

15.4

12.5 / 9.3

10 / 7.5

3TE7111-2CC21-1Axx

3TS3311-0Axx-08K

3UW5202-2C

16–25

 32A

2.5

19.5

19.5

12.5 / 9.3

3TE7111-2DC23-1AZ8 3TS3511-0AZ8-08K 3US5600-2D8K

20–32

63A

4

25

15 / 11

3TE7111-2CC24-1Axx

3TS3411-0Axx-08K

3UW5202-2C

16–25

 32A

4

23

15 / 11

3TE7111-2QC24-1AZ8 3TS3511-0AZ8-08K 3US5600-2Q8K

25–36

63A

10

29

17.5 / 13

3TE7111-2RC25-1AZ8 3TS3611-0AZ8-08K 3US5600-2R8K

32–40

80A

10

34

* Recommended Max. Back-up HRC Fuse rating, SIEMENS Make type 3NA7 – 500V

Table 3: Spares list

Description

Order No.

Contactor

3TS3210-0AZ6-08K

Contactor

3TS3210-0AZ8-08K

Contactor

3TS3311-0AZ6-08K

Contactor

3TS3311-0AZ8-08K

Contactor

3TS3411-0AZ6-08K

Contactor

3TS3411-0AZ8-08K

Contactor

3TS3511-0AZ8-08K

Contactor

3TS3611-0AZ8-08K

Thermal Overload Relay

3UW5102-2A

Thermal Overload Relay

3UW5102-2B

Thermal Overload Relay

3UW5202-2C

Thermal Overload Relay

3US5600-2D8K

Thermal Overload Relay

3US5600-2Q8K

Thermal Overload Relay

3US5600-2R8K

Coil for 200-400V

3TY7403-0AZ6

Coil for 260-460V (Z8)
For 3TS32/33/34 contactor

3TY7403-0AW415

Coil for 260-460V (Z8)
For 3TS35/36 contactor

3TY7443-0AW415

1NO Contact Block

3SB5420-0B

1NC Contact Block

3SB5420-0C

Amber LED

3SB5285-6HL33

LMRA for 260-460V

7UG0613-0FF20

LMRA for 200-400V

7UG0613-0FE20

Selection of contactor coil and LMRA

Coil voltage 

code

xx

Coil voltage 

(VAC)

Line Monitoring 

Relay 

Z6

200 - 400 

7UG0613-0FE20

Z8

260-460 

7UG0613-0FF20

Table 2: Terminal torque values

Type

Screw 

Size

Torque 

(Nm)

3TS30..32 

M3.5

0.8-1.4

3TS33/34

M4

1.0-1.5

3TS35/36

M4

2.5-3.0

(TB1/2) Terminal block 30A

M4

0.8-1.4

(TB1/2) Terminal block 60A

M5

1.5-2.1

Contact block 3SB5

M3.5

0.8-1.2

Aux terminal of 3TS 30/32

M3.5

0.8-1.1

3TY7561..Aux Terminals

M3.5

0.8-1.1

Coil Terminals A1/A2

M3.5

0.8-1.2

Aux. terminals of all Relays

M3.5

0.8-1.2

3UW51/52

M4

1.0-1.5

3US56

M5

2.5-3.0

Indicating light - Amber

M3

0.8-0.9

NOTE: 

Contact sales for ON & OFF Push Button, Terminal block 30A/60A.

For more Technical details like LMR-A wiring, operating sequence, tightening torque, mounting details etc.,  
refer Installation & Troubleshooting guide no. A5E50797230A.

Summary of Contents for RAJA+ 3TE7111-2SC18-1A Series

Page 1: ...ng Dial 6 Relay Red Test button 7 Contactor Incoming Terminal Screws 8 Contactor Outgoing Terminal Screws 9 Wiring diagram Label 10 Links 11 Gasket 12 Grommet 13 Enclosure mounting holes 4x 14 Terminal Block TB1 15 Terminal Block TB2 16 Amber LED 17 LMRA 18 LMRA mode selector switch 19 Earthing for customer Fig 1 ADOL Starter Fig 2 ADOL Starter inside view Please read and understand these instruct...

Page 2: ...is closed Rotate the Latch away from OFF push button Check the status of amber LED Ensure that amber LED is continuously ON and then only proceed Switch ON the starter by pressing the green push button marked I Fig 1 on starter door To Switch OFF the starter press red push button marked O Fig 1 on the starter door Reset Operation If the overload relay trips Reset manually Allow a reset time of app...

Page 3: ...ay 3UW5102 2A Thermal Overload Relay 3UW5102 2B Thermal Overload Relay 3UW5202 2C Thermal Overload Relay 3US5600 2D8K Thermal Overload Relay 3US5600 2Q8K Thermal Overload Relay 3US5600 2R8K Coil for 200 400V 3TY7403 0AZ6 Coil for 260 460V Z8 For 3TS32 33 34 contactor 3TY7403 0AW415 Coil for 260 460V Z8 For 3TS35 36 contactor 3TY7443 0AW415 1NO Contact Block 3SB5420 0B 1NC Contact Block 3SB5420 0C ...

Page 4: ...ough authorized dealer PLASTICS Segregate as per material type for recycling through authorized dealer Because of the long lifetime of Siemens Products the disposal guidelines may be replaced by other national regulations when taking the product out of service The local customer care service is available at any time to answer disposal related questions Customer Care Toll free no 1800 220 987 Email...

Reviews: