Technical data
Operating voltage
DC 3 V (2 x 1.5 V AA alkaline batteries)
Battery life
>1 year (AA alkaline batteries)
Thermistor
10 kΩ ± 1% at 25 °C
Switching differential SD
1 K (fixed)
Setpoint setting range
5…30 °C (Comfort mode)
5…30 °C (Energy Saving mode)
5 °C (Frost Protection, fixed value)
Factory setting comfort setpoint
20 °C
Factory setting for energy saving mode 10 °C
Resolution of settings and displays
Setpoints
0.5 °C
Actual value displays
0.5 °C
Display of time of day
1 min
Operation
IEC 60721-3-3
Climatic conditions
Class 3K5
Temperature
0…+40 °C
Humidity
<90% r.h.
Transport
IEC 60721-3-2
Climatic conditions
Class 2K3
Temperature
-25…+60 °C
Humidity
<95 % r. h.
Mechanical conditions
Class 2M2
Storage
IEC 60721-3-1
Climatic conditions
Class 1K3
Temperature
-10…+60 °C
Humidity
<90% r.h.
EU Conformity (CE)
CE1T10886xx
*)
N 4 7 4
C-tick
conformity to
Test standards and requirements EN 61000-6-3, AS/NZS 4251.1
Test standards for radio equipment AS/NZS 4268
Safety class
III as per EN 60950-1
Pollution degree
2
Degree of protection of housing
IP20
Weight (including package)
RDJ10RF/SET
515 g
Color of housing front
Signal-white RAL9003
Housing material
ABS (LCD lens: PC)
Power supply
Operational data
Environmental conditions
Standards
General