background image

6 / 13

Siemens

RDD100.1RFS  Wireless room thermostat with LCD

CB1N1424en

Building Technologies

2017-11-21

Commissioning notes

After power is applied, the thermostat carries out a reset during which all LCD
segments flash, indicating that the reset is correctly made. After the reset, the
thermostat is ready for commissioning by qualified HVAC personnel.

The control parameters of the thermostat can be set to ensure optimum
performance of the entire system (refer to Operating Instructions CB1B1424en,
section "Do you want to change parameters?").

If the temperature shown on the display does not agree with the room temperature
effectively measured, the temperature sensor can be recalibrated. For that
purpose, adjust parameter P04.

We recommend to review the setpoint setting range and setpoint lock (for public
spaces) using parameters P05…P08 and change them as needed to achieve
maximum comfort and energy savings.

Since the thermostat uses touch technology and to minimize battery power
consumption, a parameter P21 (adjustable from 0.25 to 1.5 seconds) is
implemented for the user to adjust.
This means that when, for a certain time, the user does not touch the touchpad, the
unit operates in power saving mode and the touchpad is running at a scanning rate
of 1 second.
(From the calculation – assuming 4 operations per day on the thermostat, the
estimated 1-second scanning rate results in a battery life of 1 year. If the user
increases the scanning rate, the batteries’ life is extended.)

If the battery symbol

 appears, the batteries are almost exhausted and should

be replaced. Use alkaline batteries type AAA.

For the pairing process between transmitter and receiver, refer to Operating
Instructions CB1B1424en, section "Do you want to pair transmitter and receiver?".
The table below describes the behavior of the RCR100RF:

State of receiver

State of LED

Power up (or reset)

The red and green LEDs flash alternately for 5
seconds and then change to constantly red.
Note: If the receiver was programmed before, it
will immediately change to constantly red.

Learning mode
Successful learning mode

The red and green LEDs flash alternately.
If learning was successful, the green LED will
flash for 10 minutes.

Signal ok and output status
change

The green LED is lit. If the output state changes,
the green LED flashes for 3 seconds and then
changes back to constantly green.

Fails to receive wireless data 

If the RCR100RF fails to receive wireless data,
the red LED will start to flash after 125 minutes.
 If the RCR100RF signal is recovered, it will
resume the previous LED state.

Commissioning

Sensor calibration

Setpoint and setpoint
lock

Touchpad scanning
rate

Change of batteries

LED indication on
RCR100RF

Override via the
RCR100RF

Summary of Contents for RDD100.1RF

Page 1: ...gies RDD100 1RF RCR100RF Wireless room thermostat with LCD RDD100 1RFS or heating systems oom temperature control Comfort Economy and Protection mode position control with On Off control output Adjustable commissioning and control parameters attery powered room thermostat DC 3 V RDD100 1RF ains powered receiver AC 230 V RCR100RF Building Technologies 1424 RDD100 1RFS Adjustable commissioning and c...

Page 2: ...missioning and control parameters Standalone wireless transmitter and receiver Wireless operating frequency 433 MHz Temperature control The RDD100 1RFS acquires the room temperature with its built in sensor and maintains the setpoint by delivering control commands The switching differential is 1 K Q14 T C ON OFF W SD 1424D01 T Room temperature SD Switching differential W Room temperature setpoint ...

Page 3: ...temperature sensor Mounting plate with screw terminals Table stand The housing engages in the mounting plate and is secured with a The optional table stand snaps onto the rear of the mounting plate The RCR100RF receiver consists of 2 parts Plastic housing which accommodates the electronics Mounting plate with screw terminals RDD100 1RF 1 Touchkey for o 2 Touchkey for increasing a value 3 Touchkey ...

Page 4: ...cription Symbol Description 1 Indicating that batteries need to be replaced 7 Touchkey lock activated 2 Comfort mode 8 Display of zone default is 1 3 Economy mode 9 C Room temperature in degrees Celsius 4 Display of room temperature setpoint etc 10 Heating On 5 F Room temperature in degrees Fahrenheit 11 Current room temperature 6 Protection mode Protection mode icon can be enabled via parameter s...

Page 5: ...uipment microwaves etc Do not mount near larger metallic structures or constructional elements with fine metal meshes such as special glass or special concrete See Mounting Instructions CB1M1439xx enclosed with the thermostat Ensure that wiring protection and earthing comply with local regulations Correctly size the cables to the thermostat and the valve actuators Use only valve actuators rated fo...

Page 6: ...1 second From the calculation assuming 4 operations per day on the thermostat the estimated 1 second scanning rate results in a battery life of 1 year If the user increases the scanning rate the batteries life is extended If the battery symbol appears the batteries are almost exhausted and should be replaced Use alkaline batteries type AAA For the pairing process between transmitter and receiver r...

Page 7: ...en Comfort Economy and Protection mode is made by pressing touchkey When Comfort mode is activated symbol appears on the display The setpoint 20 ºC can be readjusted by pressing touchkeys and When Economy mode is activated symbol appears on the display The setpoint 16 ºC can be readjusted by pressing touchkeys and If the temperature falls below 5 ºC the thermostat automatically activates the heati...

Page 8: ...5 C WARNING Electrolyte leakage Chemical burns Only grasp damaged batteries using suitable protective gloves If electrolyte comes into contact with eyes immediately rinse eyes with plenty of water Consult a doctor Observe the following Only replace batteries with batteries of the same type and from the same manufacturer Observe the polarities The batteries must be new and free from damage Do not m...

Page 9: ...tions Temperature Humidity Mechanical conditions As per IEC 60721 3 2 Class 2K3 25 60 C 95 r h Class 2M2 Storage Climatic conditions Temperature Humidity As per IEC 60721 3 1 Class 1K3 25 60 C 95 r h EU Conformity CE CE1T1420xx RCM conformity CE1T1420en_C1 Safety class II as per EN 60730 1 EN 60730 2 9 Pollution class II as per EN 60730 1 Degree of protection of housing IP30 as per EN 60529 The pr...

Page 10: ...ection with max C 10 A circuit breaker in the supply lines required under all circumstances External protection for incoming cable Circuit breaker Circuit breaker tripping characteristic Max 10 A Type B C or D to EN 60898 60947 Contact life at AC 230 V A res Guide value 1 x 10 5 cycles Insulating strength Between relay contacts and coil Between relay contacts same pole AC 5 000 V AC 1 000 V Connec...

Page 11: ...tuating device L N AC 230 V Lx Nx AC 24 230 V Application examples T T F1 F2 N2 M1 Y2 1424S01 N1 T F1 F2 N2 M1 Y2 1424S02 T T T N1 Wireless room thermostat with receiver control of a gas fired wall hung boiler Wireless room thermostat with receiver control of a gas fired floor standing boiler Y1 1424S03 M1 N2 T N1 F1 Thermal reset limit thermostat F2 Safety limit thermostat M1 Circulating pump N1 ...

Page 12: ...mostat with LCD CB1N1424en Building Technologies 2017 11 21 Dimensions Room thermostat RDD100 1RF 85 106 39 8 25 5 83 5 4 1 7 1 21 5 0 5 82 93 1424M01 Ø80 Ø60 Receiver RCR100RF 7 1 4 1 83 5 0 5 27 5 84 103 2 Ø5 5 Ø80 Ø60 1424M02 Dimensions in mm ...

Page 13: ...017 11 21 Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH 6300 Zug Tel 41 58 724 24 24 Siemens Switzerland Ltd 2013 2017 Technical specifications and availability subject to change without notice www siemens com buildingtechnologies ...

Reviews: