Functions 

.
.
.

 

Q14

T[°C]

ON

OFF

W

SD

30

30

D

0

1

 

 

T Room 

temperature 

SD Switching 

differential 

Room temperature setpoint 

Q14 

Output signal for heating 

Function diagram 

 

Operating modes 

The RDE10.1DHW provides auto, normal operation, energy saving (or OFF) or frost 
protection mode. The difference between normal operation and energy saving mode is 
merely the room temperature setpoint. The changeover from normal operation to en-
ergy saving or frost protection mode, or vice versa, is made by pressing a button. 
In auto mode changeover between operating modes is accomplished automatically 
according to the 7-day switching pattern. 

 

Normal operation 

When normal operation is activated, symbol 

 appears on the display. The setpoint 

can be readjusted by pressing buttons  , 

+

  

and 

-

.

 

Energy saving or OFF 

When energy saving mode is activated, symbol   appears on the display. The setpoint 

can be readjusted by pressing buttons  , 

+

  

and 

-

In energy saving mode, the unit can also be switched to OFF. This is accomplished by 

selecting a setpoint of 5 °C and then keeping button 

-

 

depressed for 4 seconds. In 

that case, symbol   does not appear. 

When frost protection mode is activated, symbol 

 appears on the display. 

Frost protection 

7-day time switch 

The changeover between “normal” and “energy saving” temperature setpoints can take 
place either automatically (

) or manually (

,  ), depending on the selection of the 

operating mode. 
When pressing the operating mode button until 

 appears on the display, changeover 

will take place automatically according to the selected switching pattern. A specific 
switching pattern can be selected for every weekday. 
Factory setting: 

Day(s) 

Normal operation 

Energy saving mode 

Mo (1) – Fr (5)  6:00 – 8:00 h and 

17:00 – 22:00 h 

22:00 – 6:00 h and 
08:00 – 17:00 h 

Sa (6) – Su (7) 7:00 – 22:00 h 

22:00 – 7:00 h 

 

The current setpoint can be temporarily readjusted by pressing buttons 

+

  

and 

-

. The 

setpoint will then be reset to its initial value the next time automatic or manual change-
over takes place. 
When the operating mode button is set to  

 or  , the controller will maintain normal 

operation or energy saving mode respectively. 
 
 
 

DHW mode 

The RDE10.1DHW features independent control of DHW. 
 
 
 

2/8 

Building Technologies 

Room temperature controller RDE10.1DHW  

CE1N3038en 

HVAC Products 

 

20.10.2005 

Summary of Contents for RDE10.1DHW

Page 1: ...h and manual control Battery powered DC 3 V 2 x 1 5 V AA Use The RDE10 1DHW is used for the control of the room temperature in heating systems with independent control of DHW Typical applications Residential apartments For the control of the following plant components and of DHW Thermal valves or zone valves Gas or oil burners Fans Pumps Heat exchanger Continuous flow water heater Small water heat...

Page 2: ... then keeping button depressed for 4 seconds In that case symbol does not appear When frost protection mode is activated symbol appears on the display Frost protection 7 day time switch The changeover between normal and energy saving temperature setpoints can take place either automatically or manually depending on the selection of the operating mode When pressing the operating mode button until a...

Page 3: ... and flashing the DHW output is activated When no segment is displayed the DHW output is deactivated Upper row with switching pattern for DHW control 3 8 Building Technologies Room temperature controller RDE10 1DHW CE1N3038en 0 6 24 12 18 C 0 6 24 12 18 C 0 6 24 12 18 C DHW Auto mode DHW ON mode DHW OFF mode Lower row with switching pattern for heating When the segment is displayed and flashing th...

Page 4: ...30 mm ARG70 2 Mechanical design The controller consists of 2 parts Plastic housing with digital display which accommodates the electronics the oper ating elements and the built in room temperature sensor Mounting base The housing engages in the mounting base and snaps on The base carries the screw terminals 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 19 17 18 16 20 3038Z05 1 Display of the room temperatur...

Page 5: ...r can be fitted to a recessed conduit box Only authorized staff may open the unit Caution AC 230 V The cables used must satisfy the insulation requirements with regard to mains potential Mounting installa tions and commis sioning When mounting the controller fix the base first Then make the electrical connections and fit and secure the cover also refer to the relevant Mounting Instructions The con...

Page 6: ...nergy saving 0 OFF and 5 35 C Factory setting normal operation 20 C Factory setting energy saving 8 C Frost protection 5 C fixed Resolution of settings and displays Setpoints 0 5 C Switching times 60 min Actual temperature value displays 0 5 C Time of day displays 1 min Operational data Operation to IEC 721 3 3 Climatic conditions class 3K5 Temperature 0 50 C Humidity 95 r h Transport to IEC 721 3...

Page 7: ... Q22 Q24 inverse of Q24 3038A02 3V Lx Nx AC 24 250 V max 5 2 A Legend Y1 Heating valve or wall hung boiler Y2 DHW heating equipment Application examples T T F1 F2 N1 M1 Y2 3033S01 T DHW T F1 F2 N1 M1 Y2 3033S02 T T DHW Room temperature controller with direct control of a gas fired wall hung boiler and independent control of DHW Room temperature controller with direct control of a gas fired floor s...

Page 8: ...ith manual adjustment Magnetic valve DHW heating equipment Room temperature controller with direct control of a heating circuit pump precontrol by manual mixing valve and independent control of DHW Dimensions Controller and base 8 8 Building Technologies Room temperature controller RDE10 1DHW CE1N3038en 2005 Siemens Switzerland Ltd Subject to alteration HVAC Products 20 10 2005 ...