Operating Instructions
CB1B1425en_01 / 2014-11-26
Siemens Building Technologies
Does symbol
appear on the display?
Symbol
is displayed when the batteries are low.
Replace them with 2 new alkaline batteries type AAA.
Proceed as follows:
·
Get 2 new alkaline batteries type AAA
·
Remove the battery holder and then the batteries.
Insert the new batteries and, within 1.5 minutes,
replace the battery holder
·
Ensure the exhausted batteries are disposed of
correctly, in compliance with environm ental
requirements
Do you want to lock the keypad?
Mode
Press and hold
Mode
for at least 7 seconds to
activate a button lock. Repeat to unlock.
The unit operates normally when the buttons
are locked, but changes cannot be made.
Receiver’s LED indication
State of receiver
State of LED
Power up (or reset)
The red and green LEDs flash
alternately for 5 seconds, then
change to constantly red.
Note: If the receiver was previ-
ously programmed, it shows
immediately constantly red.
Learning mode
Successful learning
mode
The red and green LEDs flash
alternatively.
If RCR100RF learning is
successful, the green LED will
flash for 10 minutes.
Signal ok and
output status
change
The green LED is constantly lit,
and if the output status
changes, the green LED flashes
for 3 seconds, then changes
back to constantly green.
Fail to receive
wireless data
If the RCR100RF fails to receive
wireless data, the red LED will
start to flash after 125 minutes.
If the RCR100RF signal is
recovered, it will return to the
previous LED state.
Do you want to change parameters?
+
–
Ok
Mode
If you want to change control parameters,
proceed as follows:
·
Press
+
and
–
simultaneously for 5
seconds
·
Release the buttons and parameter
P01 is displayed on the bottom
segment
·
Press
+
or
–
to scroll to the parameter
that needs to be changed
·
Press
Ok
to select the parameter
·
Press
+
or
–
to change the value
·
Press
Ok
to confirm the changed value
·
Press
Mode
to exit the parameters
without saving or wait for the program
to exit automatically
Parameter list
Parameter
no.
Description
Setting range
(default)
P01
Time format
1 = 24:00 hours
(default)
2 = 12:00 am/pm
P02
Selection of °C or
°F
1 = °C (default)
2 = °F
P03
Standard
temperature display
1 = room temperature
(default)
2 = setpoint
P04
Temperature
sensor calibration
-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C
P06
Comfort setpoint
lock
0 = OFF (default)
1 = ON
à
locked
according to setting
in permanent
temperature setpoint
P08
Economy setpoint
lock
0 = OFF (default)
1 = ON
à
locked
according to setting
in permanent
temperature setpoint
P09
Buzzer
0 = OFF
1 = ON (default)
P10
Show frost
protection icon
0 = OFF (default)
1 = ON
P11
Time switch type for
Auto Timer
0 = individual days
(default)
1= all 7 days
2= 5-2 days
P12
Periodic pump run
0 = OFF (default)
1 = ON
P14
X1 external input
0 = no input (default)
1 = external sensor
2 = digital input
P15
Temperature
limitation
0 = OFF (default)
1 = ON
P16
Max. limitation
temperature for
floor heating
35…60 °C, step 1 °C
or
95…140 °F, step 1 °F
Default: 55 °C
P17
Window contact
features
0 = normally open
contact (default)
1 = normally closed
contact
P19
Sequential number
of room unit
0 = no display of
zone (RF off)
1 = zone number 1
(for standard RF)
(default)
6 = zone number 6
P20
RF learn
0 = OFF (default)
1 = ON
P21
Scanning rate for
the capacitive
buttons
Note: Shorter
scanning rate
means shorter
battery life
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
P22
Reload factory
settings
0 = OFF (default)
1 = reload
P23
Software version
information
No adjustment
possible