background image

3/8 

Siemens 

Room temperature controllers 

CE1N3036en 

Building Technologies 

 

13.10.2008 

The digital display shows the actual room temperature, the time of day, the weekday, 
the current switching pattern and the symbol of the operating mode currently active. 
The switching pattern shows normal operation as a double bar and energy saving 
mode as a single bar with a flashing time pointer. When the heating output is activated, 
the triangle symbol appears. 

0

6

12

18

24

 

0

6

12

18

24

 

0

6

12

18

24

 

Automatic changeover according 

Normal operation 

Energy saving mode 

to the switching pattern 

 
When taking out the batteries, the setpoints and the information required for operating 
mode changeover are retained for 3 minutes.  

Ordering 

When ordering, please give name and type reference: room temperature controller 
RDE20.1. 
Sensor and valve actuators are to be ordered as separate items. 

Equipment combinations 

Type of unit 

Type reference 

Data sheet 

Temperature sensor

 

QAH11 

1840 

Room sensor 

QAA32 

1747 

Electromotoric actuator 

SFA21... 

4863 

Electrothermal actuator (for radiator valve) 

STA21... 

4877 

Electrothermal actuator (for small valve 2,5 mm) 

STP21... 

4878 

2-port and 3-port zone valves 

MXI/MVI421… 

4867 

Electromotoric actuator for zone valve V..146.. 

SUA21 

4830 

Electric actuator  

SUA11/22 

4832 

Air damper actuator 

GDB… 

4624  

Air damper actuator 

GSD/GQD… 

4606 

Rotary damper actuators 

GXD… 

4622 

16A extension relay module 

SEZ16 

Accessories 

 

Description Type 

reference 

Adapter plate 120 x 120 mm for 4“ x 4“

 

conduit

 

boxes ARG70 

Adapter plate   96 x 120 mm for 2“ x 4“

 

conduit

 

boxes  

ARG70.1 

Adapter plate for surface wiring 112x130 mm 

ARG70.2 

Display 

Backup 

Summary of Contents for RDE20.1

Page 1: ...ing Operating modes normal operation and energy saving mode 7 day time switch and manual operation Battery powered DC 3 V Input for external temperature sensor Use The RDE20 1 is used for the control of the room temperature in heating systems Typical applications Apartments Commercial spaces Schools For the control of the following pieces of equipment Thermic valves or zone valves Gas or oil burne...

Page 2: ...on the display The setpoint can be readjusted by pressing buttons and When energy saving mode is activated symbol appears on the display The set point can be readjusted by pressing buttons and In energy saving mode the unit can also be switched to Off This is accomplished by selecting a setpoint of 5 C and then keeping button depressed for 4 seconds In that case the OFF will appear and the symbol ...

Page 3: ...es Ordering When ordering please give name and type reference room temperature controller RDE20 1 Sensor and valve actuators are to be ordered as separate items Equipment combinations Type of unit Type reference Data sheet Temperature sensor QAH11 1840 Room sensor QAA32 1747 Electromotoric actuator SFA21 4863 Electrothermal actuator for radiator valve STA21 4877 Electrothermal actuator for small v...

Page 4: ...ay from 1 Monday to 7 Sunday 4 Current switching pattern with flashing time pointer 5 symbol when actual room temperature is displayed 6 Normal operation Energy saving mode 7 symbol in automatic mode or when selecting the switching pattern 8 heating on 9 symbol indicating that batteries need to be replaced 10 Buttons for adjusting the setpoints the time of day and the switching times 11 Operating ...

Page 5: ... recalibrated For that purpose both buttons and must be pressed simultaneously for 3 seconds Then the temperature displayed can be changed by a maximum of 10 K by pressing the and but tons Five seconds after the last push of a button the controller will automatically return to the normal operational status The setpoint limitation is used in some specific applications where the setpoint tem peratur...

Page 6: ...trength Between relay contacts and coil AC 3750 V for 6 sec AC 2000 V for 60 sec Between relay contacts same pole AC 1000 V for 60 sec Switching differential SD 1 K Setpoint setting range 5 35 C normal operation 5 60 C with setpoint limitation 0 OFF and 5 35 C energy saving mode Factory setting normal operation 20 C Factory setting energy saving mode 8 C Resolution of settings and displays Setpoin...

Page 7: ...N 61000 6 3 Immunity domestic sector light ind EN 61000 6 1 Safety class II to EN 60730 Pollution degree 3 Degree of protection of housing IP30 to EN 60529 Weight 0 21 kg Colour of housing front white RAL 9003 Housing material ABS Slider POM LCD Lens GP PS Connection diagram Application examples T T F1 F2 N1 M1 Y2 2222S01 T T F1 F2 N1 M1 Y2 2222S02 T T Room temperature controller with direct Room ...

Page 8: ...th direct control of a heating circuit pump precontrol by manual mixing valve F1 Thermal reset limit thermostat F2 Safety limit thermostat M1 Circulating pump N1 RDE20 1 room temperatures controller Y1 3 port valve with manual adjustment Y2 Magnetic valve Dimensions 96 119 23 8 3035M01 89 45 4 3035M02 28 28 28 28 26 30 35 30 11 8 112 3 4 Controller Baseplate 2003 2008 Siemens Building Technologies...