After applying power, the controller makes a reset during which all LCD segments flash, 
indicating that the reset has been correctly made. This takes about 3 seconds. Then, 
the controller is ready for commissioning by qualified HVAC staff. The control 
parameters of the controller can be set to ensure optimum performance of the whole 
system (also refer to “Setting the control parameters”). 

 

  Only with RDF110: Depending on the application, the heating / cooling mode needs 

to be set via parameter P22. Factory setting is “Cooling only”. When using the 
”Automatic heating / cooling changeover” function, P22 must be set to “Automatic 
H/C changeover”.  
Note: When P22 is set to “Automatic H/C changeover”, the built-in sensor is used 
for acquiring the room temperature 

  If the controller is used in conjunction with a compressor, the minimum output on 

time (parameter P15) and off time (parameter P16) of Y11 must be adjusted in order 
not to harm the life time of the compressor 

  If the room temperature displayed by the controller does not accord with the room 

temperature effectively measured, the temperature sensor can be recalibrated. In 
that case, parameter P07 must be changed 

  For comfort and energy saving reasons, it is suggested to review the setpoints and 

setpoint ranges (parameters P01…P06) and, if necessary, to change them 
accordingly 

  Only with RDF110: Parameters P98 and P99 are diagnostic values and help check 

the system. With P98, the status of the active temperature sensor is shown and, 
with P99, the status of the heating / cooling changeover sensor 

Disposal 

The devices are considered electronics devices for disposal in term of European 
Directive 2012/19/EU and may not be disposed of as domestic waste. 

  Dispose of the device via the channels provided for this purpose 

  Comply with all local and currently applicable laws and regulations. 

 
 

Technical data  

Operating voltage 

AC 230 V +10/-15 % 

Frequency 

50/60 Hz 

Power consumption 

max. 8 VA 

No internal fuse 

External preliminary protection with max. C 10 A circuit breaker in the supply line 

required under all circumstances 

Fan control Q1, Q2, Q3-N

 

Rating 

AC 230 V 

5 mA…4(2)A 

Control output Y11-N (N.O.) / Y12-N (N.C.) 

Rating 

AC 230 V 

5 mA…4(2)A 

Changeover or external room temperature sensor B1-M 

Temperature sensor 

Voltage against earth 

Cable length  

 

QAH11.1, safety class II 

AC 230 V 

max. 80 m (min. 1.5 mm

2

Status input D1 and GND 

Contact sensing 

Insulation against mains 

Operating action 

Cable length  

 

SELV DC 6…15 V / 3…6 mA 

4 kV, reinforced insulation 

selectable (N.O. / N.C.) 

max. 80 m (min. 1.5 mm

2

Infrared receiver (only with RDF110…/IR) 

Transmission distance 

Orientation angle 

 

≤ 7.5 m 

≤ ± 30 ° 

Commissioning 

Heating / cooling mode 

Compressor-based 
application

 

 

Calibrating the sensor 

Setpoint and range 
limitation 

Diagnostic values 

 

 Power supply 

 

Outputs 

 

Inputs 

 

 

   

 

 

 

 

 

Summary of Contents for RDF110

Page 1: ...nt Minimum and maximum setpoint limitation Operating voltage AC 230 V Additional features of RDF110 Automatic heating cooling changeover Operating modes Normal operation Economy Energy saving and Protection Standby Input for heating cooling changeover or return air temperature sensor Potential free input for operating mode changeover key card contact etc Function for avoiding damage resulting from...

Page 2: ...with RDF110 IR Controller The controller acquires the room temperature via its built in sensor and maintains the setpoint by delivering 2 position valve control commands or compressor output commands With the RDF110 an external room temperature sensor QAA32 or external return air temperature sensor QAH11 1 can be used instead The switching differential is 2 K in heating mode and 1 K in cooling mod...

Page 3: ...ferential Heating W Room temperature setpoint SDC Switching differential Cooling Y11 Control output Valve or Compressor The valve or compressor receives the OPEN command via control output Y11 when 1 the acquired room temperature lies by half the switching differential below the setpoint heating mode or above the setpoint cooling mode and 2 control output Y11 was not energized for more than the Mi...

Page 4: ...the setpoint the control valve will close and the fan switch off Temperature dependent fan control see diagram below The individual switching differentials of the fan speeds can be adjusted via control parameters P08 P13 Heating mode Cooling mode W SDH SDH SDH2 SDH3 Valve Fan W SDC SDC3 SDC2 SDC Valve Fan Y11 Y11 Temp Temp Temp Temp Q3 Q2 Q1 Q3 Q2 Q1 3058D03 If desired fan control can be set to Te...

Page 5: ...M Heating mode The QAH11 1 cable temperature sensor for automatic heating cooling changeover can be replaced by an external switch suited for mains voltage for manual remote changeover 3058Z03 B1 M T B1 M QAH11 1 Contact open heating mode Contact closed cooling mode With parameter P99 diagnostic value automatic heating cooling changeover can be checked When parameter P22 is set to Cooling only or ...

Page 6: ... means above 49 C or below 0 C the display shows the limiting temperature in flashing figures e g 0 C or 49 C If the current setpoint is not OFF see parameters 1 4 the controller is in heating mode and the temperature is below 0 C output Y11 will be energized In all other cases Y11 is deenergized When the temperature returns to the measuring range the controller will resume Normal operation In cas...

Page 7: ...y pressing buttons and simultaneously the current value of the selected parameter appears which can be changed by repeatedly pressing buttons or 5 By pressing buttons and simultaneously again or 5 seconds after the last press of a button the last parameter will be displayed again 6 If you wish to display and change additional parameters repeat steps 3 through 5 7 10 seconds after the last display ...

Page 8: ...play of temperature or setpoint OFF Setpoint ON Room or return air temperature ON P19 Operating action of remote changeover input 0 Normally open N O 1 Normally closed N C 0 1 P20 Fan control in Economy Energy saving mode OFF in dead zone ON in dead zone OFF1 P21 Fan control in Normal operation OFF in dead zone ON in dead zone OFF P22 Heating cooling mode 0 Heating only 1 Cooling only 2 Automatic ...

Page 9: ... boxes ARG70 Adapter plate 96 x 120 mm for 2 x 4 conduit boxes ARG70 1 Adapter plate for surface wiring 112 x 130 mm ARG70 2 Ordering When ordering please prodive name and type E g room temperature controller RDF110 The IRA210 infrared remote control is to be ordered as a separate item The QAH11 1 can be used as a return air temperature or automatic heating cooling changeover sensor In case it is ...

Page 10: ...al conductive paste must be applied to the location on the pipe where the sensor is placed Also refer to the Mounting Instructions B3057 enclosed with the controller Wiring protection and earthing must be installed in compliance with local regulations It must be made certain that safety extra low voltage lines SELV circuit are clearly separated from AC 230 V mains voltage cable The cables to the c...

Page 11: ...point ranges parameters P01 P06 and if necessary to change them accordingly Only with RDF110 Parameters P98 and P99 are diagnostic values and help check the system With P98 the status of the active temperature sensor is shown and with P99 the status of the heating cooling changeover sensor Disposal The devices are considered electronics devices for disposal in term of European Directive 2012 19 EU...

Page 12: ...Setpoints Current temperature value displayed 0 5 C 0 5 C Operation Climatic conditions Temperature Humidity to IEC 60721 3 3 class 3K5 0 50 C 95 r h Transport Climatic conditions Temperature Humidity Mechanical conditions to IEC 60721 3 2 class 2K3 25 60 C 95 r h class 2M2 Storage Climatic conditions Temperature Humidity to IEC 60721 3 1 class 1K3 25 60 C 95 r h EU Conformity CE CE1T3057xx RCM Co...

Page 13: ...y open valves Only with RDF110 or RDF110 IR Connection diagrams Application 2 pipe fan coil units 3057A01 B1 Return air temperature sensor QAH11 1 or external room temperature sensor QAA32 B2 Changeover sensor temperature sensor QAH11 1 changeover mounting kit ARG86 3 M1 3 speed fan N1 Room temperature controller RDF110 S1 External operating mode changeover switch V1 Zone valve Only with RDF110 or...

Page 14: ... N3057en Building Technologies 2014 10 28 Dimensions 102 120 3 128 30 3057M02 28 28 35 30 10 15 94 85 28 7 30 4 2 5 21 85 34 15 120 3 31 65 24 35 11 8 28 28 4 3057M03 Controller Mounting base 2006 2014 Siemens Switzerland Ltd Subject to change ...

Reviews: