background image

8/14 

Siemens 

Room Temperature Controllers 

N3057en 

Building Technologies 

 

2014-10-28 

 

Para-

meter 

Meaning 

Setting range 

Factory  

setting 

P01 

Setpoint of heating in 

Economy (Energy saving) 

mode 

 

(Wheat

Eco

OFF, 5 °C…Wcool

Eco

 

16 

°

C

1)

 

P02 

Setpoint of cooling in 

Economy (Energy saving) 

mode 

 

(Wcool

Eco

OFF, Wheat

Eco

…40 °C 

28 

°

C

1)

 

P03 

Setpoint of heating in 

Protection (Standby)

   

(Wheat

Stb

OFF, 5 °C…Wcool

Stb

 

OFF 

P04 

Setpoint of cooling in 

Protection (Standby)

   

(Wcool

Stb

OFF, Wheat

Stb

 …40 °C 

OFF 

P05 

Minimum setpoint limitation in Normal operation  

(Wmin

Comf

5 °C…Wmax

Comf

 

5 °C 

P06 

Maximum setpoint limitation in Normal operation  

(Wmax

Comf

)  Wmin

Comf

…40 °C 

35 °C 

P07 

Sensor calibration 

-3…+3 K 

0 K 

P08 

Switching differential heating mode SDH 

0.5…+4K 

2 K 

P09 

Switching differential cooling mode SDC 

0.5…+4K 

1 K 

P10 

Switching differential fan speed 2 in heating mode SDH2 

0.5…+4K 

1 K 

P11 

Switching differential fan speed 2 in cooling mode SDC2 

0.5…+4K 

1 K 

P12 

Switching differential fan speed 3 in heating mode SDH3 

0.5…+4K 

1 K 

P13 

Switching differential fan speed 3 in cooling mode SDC3 

0.5…+4K 

1 K 

P14 

Dwelling time of auto fan speeds 

1…5 minutes 

2 min 

P15 

Minimum output on time (Y11) 

1…10 minutes 

1 min 

P16 

Minimum output off time (Y11) 

1…10 minutes 

1 min 

P17 

Selection of °C or °F 

°C or °F 

°C 

P18 

Display of temperature or setpoint  

OFF: Setpoint 

ON: Room (or return air) 

       temperature 

ON 

P19 

Operating action of remote changeover input 

0: Normally open (N.O)  

1: Normally closed (N.C.) 

0

1)

 

P20 

Fan control in 

Economy (Energy saving) 

mode 

OFF in dead zone  

ON in dead zone  

OFF

1)

 

P21 

Fan control in Normal operation 

OFF in dead zone  

ON in dead zone 

OFF 

P22 

Heating / cooling mode 

0: Heating only 

1: Cooling only 

2: Automatic H/C  

    changeover 

1: Cooling 

    only

1)

 

P23 

Heating / cooling changeover switching point cooling 

10…25 °C 

16 °C

1)

 

P24 

Heating / cooling changeover switching point heating 

27…40 °C 

28 °C

1)

 

P25 

Infrared receiver (only with RDF.../IR) 

0: Disabled 

1: Enabled 

P98 

Active temperature sensor  

0: Internal sensor 

1: External sensor 

Diagnostic 

value

1)

 

P99 

Value of current heating / cooling changeover temperature  

reading and indication of current mode 

100 = input open 

   mode 

0…49 °C = cur. temp. value 

00 = input bridged 

 

mode 

OFF= not commissioned as 

automatic H/C changeover 

Diagnostic 

value

1)

 

 

1) Not available with RDF110.2 

 

 

Type summary 

Type 

Features 

RDF110 

With input for automatic heating / cooling changeover or return air 

temperature sensor 

With input for operating mode changeover 

RDF110.2 

With manual heating / cooling changeover 

Without input for sensor 

Without input for operating mode changeover 

RDF110/IR 

*)

 

Same as RDF110 plus infrared remote control 

RDF110.2/IR 

*)

 

Same as RDF110.2 plus infrared remote control 

*) Type is not orderable any more 

 
 

Control parameters of the RDF110 and RDF110.2 

Summary of Contents for RDF110

Page 1: ...nt Minimum and maximum setpoint limitation Operating voltage AC 230 V Additional features of RDF110 Automatic heating cooling changeover Operating modes Normal operation Economy Energy saving and Protection Standby Input for heating cooling changeover or return air temperature sensor Potential free input for operating mode changeover key card contact etc Function for avoiding damage resulting from...

Page 2: ...with RDF110 IR Controller The controller acquires the room temperature via its built in sensor and maintains the setpoint by delivering 2 position valve control commands or compressor output commands With the RDF110 an external room temperature sensor QAA32 or external return air temperature sensor QAH11 1 can be used instead The switching differential is 2 K in heating mode and 1 K in cooling mod...

Page 3: ...ferential Heating W Room temperature setpoint SDC Switching differential Cooling Y11 Control output Valve or Compressor The valve or compressor receives the OPEN command via control output Y11 when 1 the acquired room temperature lies by half the switching differential below the setpoint heating mode or above the setpoint cooling mode and 2 control output Y11 was not energized for more than the Mi...

Page 4: ...the setpoint the control valve will close and the fan switch off Temperature dependent fan control see diagram below The individual switching differentials of the fan speeds can be adjusted via control parameters P08 P13 Heating mode Cooling mode W SDH SDH SDH2 SDH3 Valve Fan W SDC SDC3 SDC2 SDC Valve Fan Y11 Y11 Temp Temp Temp Temp Q3 Q2 Q1 Q3 Q2 Q1 3058D03 If desired fan control can be set to Te...

Page 5: ...M Heating mode The QAH11 1 cable temperature sensor for automatic heating cooling changeover can be replaced by an external switch suited for mains voltage for manual remote changeover 3058Z03 B1 M T B1 M QAH11 1 Contact open heating mode Contact closed cooling mode With parameter P99 diagnostic value automatic heating cooling changeover can be checked When parameter P22 is set to Cooling only or ...

Page 6: ... means above 49 C or below 0 C the display shows the limiting temperature in flashing figures e g 0 C or 49 C If the current setpoint is not OFF see parameters 1 4 the controller is in heating mode and the temperature is below 0 C output Y11 will be energized In all other cases Y11 is deenergized When the temperature returns to the measuring range the controller will resume Normal operation In cas...

Page 7: ...y pressing buttons and simultaneously the current value of the selected parameter appears which can be changed by repeatedly pressing buttons or 5 By pressing buttons and simultaneously again or 5 seconds after the last press of a button the last parameter will be displayed again 6 If you wish to display and change additional parameters repeat steps 3 through 5 7 10 seconds after the last display ...

Page 8: ...play of temperature or setpoint OFF Setpoint ON Room or return air temperature ON P19 Operating action of remote changeover input 0 Normally open N O 1 Normally closed N C 0 1 P20 Fan control in Economy Energy saving mode OFF in dead zone ON in dead zone OFF1 P21 Fan control in Normal operation OFF in dead zone ON in dead zone OFF P22 Heating cooling mode 0 Heating only 1 Cooling only 2 Automatic ...

Page 9: ... boxes ARG70 Adapter plate 96 x 120 mm for 2 x 4 conduit boxes ARG70 1 Adapter plate for surface wiring 112 x 130 mm ARG70 2 Ordering When ordering please prodive name and type E g room temperature controller RDF110 The IRA210 infrared remote control is to be ordered as a separate item The QAH11 1 can be used as a return air temperature or automatic heating cooling changeover sensor In case it is ...

Page 10: ...al conductive paste must be applied to the location on the pipe where the sensor is placed Also refer to the Mounting Instructions B3057 enclosed with the controller Wiring protection and earthing must be installed in compliance with local regulations It must be made certain that safety extra low voltage lines SELV circuit are clearly separated from AC 230 V mains voltage cable The cables to the c...

Page 11: ...point ranges parameters P01 P06 and if necessary to change them accordingly Only with RDF110 Parameters P98 and P99 are diagnostic values and help check the system With P98 the status of the active temperature sensor is shown and with P99 the status of the heating cooling changeover sensor Disposal The devices are considered electronics devices for disposal in term of European Directive 2012 19 EU...

Page 12: ...Setpoints Current temperature value displayed 0 5 C 0 5 C Operation Climatic conditions Temperature Humidity to IEC 60721 3 3 class 3K5 0 50 C 95 r h Transport Climatic conditions Temperature Humidity Mechanical conditions to IEC 60721 3 2 class 2K3 25 60 C 95 r h class 2M2 Storage Climatic conditions Temperature Humidity to IEC 60721 3 1 class 1K3 25 60 C 95 r h EU Conformity CE CE1T3057xx RCM Co...

Page 13: ...y open valves Only with RDF110 or RDF110 IR Connection diagrams Application 2 pipe fan coil units 3057A01 B1 Return air temperature sensor QAH11 1 or external room temperature sensor QAA32 B2 Changeover sensor temperature sensor QAH11 1 changeover mounting kit ARG86 3 M1 3 speed fan N1 Room temperature controller RDF110 S1 External operating mode changeover switch V1 Zone valve Only with RDF110 or...

Page 14: ... N3057en Building Technologies 2014 10 28 Dimensions 102 120 3 128 30 3057M02 28 28 35 30 10 15 94 85 28 7 30 4 2 5 21 85 34 15 120 3 31 65 24 35 11 8 28 28 4 3057M03 Controller Mounting base 2006 2014 Siemens Switzerland Ltd Subject to change ...

Reviews: