The supported communication objects differ in LTE- and S-Mode
∂
Changes via the local HMI or via KNX have the same priority (last always wins)
∂
Adjusting the Comfort basic setpoint resets the runtime Comfort setpoint to the
basic setpoint
∂
Central setpoint shift is used for summer/winter compensation in particular
∂
Setpoint shift does not affect the setpoints stored in P08, P11, P12 and P33
∂
Local shift and central shift are added together
∂
Applies only to Comfort and Economy setpoints; Protection setpoints are not
shifted centrally
∂
The resulting (current) setpoint heating and cooling is limited by the Protection
setpoint; if the Protection setpoint is OFF, minimum 5 °C and maximum 40 °C
are used
∂
The resulting setpoints for cooling and heating of the same operating mode have
a minimum distance of 0.5 K between them
∂
The result of local and central shift, together with the room operating mode, is
used by the thermostat for temperature control (current setpoint)